beautypg.com

3 motor filter – Lenze 8615E User Manual

Page 45

background image

43

6.3

Motor filter

Advantages of using a motor filter:

The motor filter reduces capacitive currents caused by parasitic
cable capacitances.

The slope of the motor voltage (dv/dt) is limited to 500 V/µs.

Motor filters are always required for:

unscreened cables longer than 100m.

screened cables longer than 50m.

when using motors which do not have suitable insulation for
inverter operation. (Observe data of the motor manufacturer.)

Please note:

Install the motor filter as close as possible to the inverter

- Maximum cable length 5 m

Connect +U

G

and -U

G

of the motor filter only to the inverter

terminals of the same designation.

Select the control mode "V/f characteristic control"
(C006 = -0-). The control "magnetizing current control" is not
permissible.

The chopping frequency must be at least 4 kHz.

The max. permissible output frequency is 300 Hz.

The inverter is loaded in addition to the motor current with
approx. 12% of the rated filter current.

The voltage drop across the motor filter at rated current and
rated frequency (f

d

= 50 Hz) is 2 to 3% of the inverter output

voltage.

For motor cable lengths > 100 m (screened) and > 200 m (un-
screened) a motor supply filter should be used.

With unscreened motor cables it should be tested whether the
system complies with the interference levels required for the CE-
EMC conformity.

This manual is related to the following products: