Lenze 8615E User Manual
Page 107

105
Code
Name
Parameter
(Factory settings are printed in bold)
Acceptance see
page
Your
settings
C086*
Motor frame
size
-0-
Size 71,
self-ventilated
-1-
Size 80,
self-ventilated
-2-
Size 90,
self-ventilated
-3-
Size 100,
self-ventilated
-4-
Size 112,
self-ventilated
-5-
Size 132,
self-ventilated
-6-
Size 160,
self-ventilated
-7-
Size 180,
self-ventilated
-8-
Size 200,
self-ventilated
-9-
Size 225,
self-ventilated
-10-
Size 250,
self-ventilated
-100-
Size 71,
forced-ventilated
-101-
Size 80,
forced-ventilated
-102-
Size 90,
forced-ventilated
-103-
Size 100,
forced-ventilated
-104-
Size 112,
forced-ventilated
-105-
Size 132,
forced-ventilated
-106-
Size 160,
forced-ventilated
-107-
Size 180,
forced-ventilated
-108-
Size 200,
forced-ventilated
-109-
Size 225,
forced-ventilated
-110-
Size 250,
forced-ventilated
[SH + PRG] 98
C088*
Rated motor
current
0.5
⋅
I
maxcontroller
0.15...1.0
⋅
I
maxcontroller
(in steps of 0.1A to 100A
in steps of 1A as of 100A)
[SH + PRG] 98
C092*
Pole pair
number (only
for LECOM)
2
1...6
[SH + PRG] 110
C094*
User password 000
000...999
000 = no password request
under C000
SH + PRG
99
C098
Language
-0-
German
-1-
English
-2-
French
SH + PRG
99
C099*
Software
version
-0-
86 6.4
100
C100
Preselection:
Additional
acceleration
and
deceleration
time (main set-
value)
-1-
Pair of ramp times 1
-2-
Pair of ramp times 2
...
...
-15-
Pair of ramp times 15
SH + PRG
81
C101
Acceleration
time for C100
2.5s
0.0...990 s
(in steps of 10 ms from 0.0 to 1 s
in steps of 100 ms from 1 to 10 s
in steps of 1 s from 10 to 100 s
in steps of 10 from 100 to 990 s)
ON-LINE
81
C103
Deceleration
time for C100
2.5s
0.0... 990 s
(in steps of 10 ms from 0.0 to 1 s
in steps of 100 ms from 1 to 10 s
in steps of 1 s from 10 to 100 s
in steps of 10 from 100 to 990 s)
ON-LINE
81
C105
Deceleration
time for quick
stop
5.0s
0.0...990 s
(in steps of 10 ms from 0.0 to 1 s
in steps of 100 ms from 1 to 10 s
in steps of 1 s from 10 to 100 s
in steps of 10 s from 100 to 990 s)
ON-LINE
58
C107
Holding time
for DC
injection
braking
999s
0.0...999s
999s = Holding time infinite
(in steps of 10ms from 0.0 to 1s
in steps of 100ms from 1 to 10s
in steps of 1s from 10 to 100s
in steps of 10s from 100 to 999s)
ON-LINE
79