Lenze 8615E User Manual
Page 108

106
Code
Name
Parameter
(Factory settings are printed in bold)
Acceptance see
page
Your
settings
C108
Gain for C110 1.00
-10.00...+10.00
(in steps of 0.01)
ON-LINE
89
C109
Offset for
C110
0mV
-1000...+1000mV
(in steps of 1mV)
ON-LINE
89
C110
Preselection:
monitor output
-1-
Analog output terminal 62
-2-
Analog output terminal 63
SH + PRG
89
C111
Monitor signal
for C110
-0-
No signal
-2-
Ramp generator input
(Set-value 1, JOG frequency)
-5-
Total set-value (total from main
set-value and set-value 2)
-6-
Feedback of PI controller
-7-
Output of PI controller
-9-
Output frequency
-23-
Motor current
-30-
Motor voltage
-31-
DC bus voltage
SH + PRG
89
C112
Preselection:
freely
assignable
digital input
-1-
digital input E1
-2-
digital input E2
...
...
-8-
digital input E8
SH + PRG
78,
79
C113
Function for
C112
-0-
No function
-1-
Enable additional pair of ramp times
-2-
Enable JOG frequencies
-3-
Reset TRIP
-4-
Set TRIP
-5-
Activate DC injection braking
-7-
Integral action component = 0
-9-
Ramp generator stop
-10-
Ramp generator input = 0
-13-
Activate process control
-20-
Select parameter set
-21-
Load parameter set
[SH + PRG] 78,
79
C114
Polarity for
C113
-0-
Input HIGH active
-1-
Input LOW active
[SH + PRG] 78,
79
C115
Priority for
C113
-0-
Function can be changed via C001
-1-
Function can be activated via terminals
independently of C001
[SH + PRG] 78,
79
C116
Preselection:
freely
assignable
digital output
-1-
Digital output A1
-2-
Digital output A2
-3-
Digital output A3
-4-
Digital output A4
-5-
Relay output K11/K14
SH + PRG
86,
87
C117
Function for
C116
-0-
No function
-1-
Output frequency smaller than
Q
min
-threshold
-3-
Maximum current reached
-4-
Ready
-5-
Pulse inhibit
-6-
Fault indication
-9-
Set-value reached
-10-
Feedback = set-value
-11-
Feedback = 0
-14-
Flying restart circuit active
-30-
Process control active
-31-
Process step 1 active
-32-
Process step 2 active
-33-
Process step 3 active
-34-
Process step 4 active
-35-
Process step 5 active
-36-
Process step 6 active
-37-
Process step 7 active
-38-
Process step 8 active
SH + PRG
86,
87
C118
Polarity for
C117
-0-
Output HIGH active
-1-
Output LOW active
SH + PRG
86,
87