9code table – Lenze 8615E User Manual

Page 103

background image

101

9

Code table

The following table shows which settings you can enter under which
codes. For detailed explanations of the codes and their possible
functions refer to the corresponding chapters.

How to read the code table:

Column

Abbreviation

Meaning

Code

C000
C005*

Code of the standard code set
Code of the extended code set

Parameter

-0-

Factory settings are printed in bold.

Acceptance

ON-LINE
SH + PRG
[SH + PRG]

Controller immediately accepts the new parameter
Controller accepts the new parameters after pressing SH + PRG
Controller accepts the new parameters only if the controller is inhibited when
pressing SH + PRG.

Code

Name

Parameter
(Factory settings are printed in bold)

Acceptance see

page

Your
settings

C000

Code set

-0-

Standard code set read only

-1-

Standard code set

-2-

Extended code set

-9-

Service code set

SH + PRG

54,
99

C001

Operating
mode

Control

Programming

-0-

Terminals

Keypad

-1-

Keypad

Keypad

-2-

Terminals

LECOM 1(X6)

-3-

LECOM 1 (X6)

LECOM 1 (X6)

-4-

Terminals

LECOM 2

-5-

LECOM 2

LECOM 2

-6-

LECOM 2

Keypad

-7-

LECOM 2

LECOM 1

[SH + PRG] 57

C002

Load
parameter set

-0-

Factory setting

-1-

Parameter set 1

-2-

Parameter set 2

-3-

Parameter set 3

-4-

Parameter set 4

[SH + PRG] 56,

85

C003

Store
parameter set

-1-

Parameter set 1

-2-

Parameter set 2

-3-

Parameter set 3

-4-

Parameter set 4

SH + PRG

56,
85

C004

Switch-on
display

xxx

Code number for display after mains
connection

SH + PRG

100

C005

Configuration

-0-

Open-loop control, unipolar,
without set-value 2
With -0- and operation via serial
interface,the set-value can be entered
bipolar under C046.

-1-

Open-loop control, bipolar

-2-

Open-loop control with digital frequency

-11-

Closed-loop control with analog
feedback

-13-

Closed-loop control with
incremental encoder feedback

-14-

Closed-loop control with digital
frequency set-value via X8 and
incremental encoder feedback via X5

-15-

Closed-loop control with digital frequency
set-value via X5 and incremental
encoder feedback via X8

[SH + PRG] 60,

73

C006

Control mode

-0-

V/f characteristic control

-1-

I0 -control

[SH + PRG] 67