In case of control via the keypad or the LECOM interface, quick
stop can also be (de-)activated via C042.
Code
Parameter
Meaning
Acceptance
C042
-0-
-1-
Deactivate quick stop
Activate quick stop
SH + PRG
If you want to deactivate quick stop:
•
Apply a voltage between 13 and 30V across terminals 21 or 22
(CCW rotation).
•
If you have set C042 to -1- via the keypad or one of the
LECOM interfaces, deactivate quick stop in addition by setting
C042 to -0-.
Select direction of rotation
When operating with terminal control, not only the quick stop is
deactivated by applying a HIGH signal across terminal 21 or 22,
but also the direction of rotation is selected. Depending on the
terminal, CW or CCW rotation results from a positive main set-
value (set-value 1/JOG frequency).
Meaning
(C176 = -0-)
Terminal
21
Terminal
22
Display
C041
Display
C042
Quick stop active
Quick stop not active
−
Main set-value not inverted
Quick stop not active
−
Main set-value inverted
LOW
HIGH
LOW
LOW
LOW
HIGH
-x-
-0-
-1-
-1-
-0-
-0-
If you have selected a configuration with additional set-value (see
page 48), please note that a change of the direction of rotation only
inverts the main set-value, not set-value 2.
Changing the functions of terminals 21, 22
Code C176 can be used to arrange the functions of terminals 21
and 22 such that quick stop and CW/CCW rotation are independent
of each other.
Code
Parameter
Meaning
Acceptance
C176
-0-
-1-
Term. 21: Deactivate quick stop
Term. 22: Deactivate quick stop,
invert main set-value
Term. 21: Invert main set-value
Term. 22: Deactivate quick stop
[SH + PRG]
The following table shows the terminal function for C176 = -1-.
Meaning
(C176 = -1-)
Terminal
21
Terminal
22
Display
C041
Display
C042
Main set-value not inverted
Main set-value inverted
Quick stop active
Quick stop not active
LOW
HIGH
x
x
x
x
LOW
HIGH
-0-
-1-
-x-
-x-
-x-
-x-
-1-
-0-
In case of wire breakage at terminal 21, the drive may change its
direction of rotation.