beautypg.com

Lenze 8615E User Manual

Page 105

background image

103

Code

Name

Parameter
(Factory settings are printed in bold)

Acceptance see

page

Your
settings

C025

Preselection:
Encoder

-1-

Analog input X1/terminals 1/2

-2-

Analog input X1/terminals 3/4

-4-

Analog input X1/terminal 8

-10-

Digital frequency/incremental encoder
input X5

-11-

Digital frequency/incremental encoder
input X8

SH + PRG

66,
73

C026

Constant for
C025

For analog inputs:
xxxx mV factory setting

-1000...+1000mV
(in steps of 1mV)

For digital frequency/incremental encoder inputs:
-1-

512 pulses/Hz or increments/revolution

-2-

1024 pulses/Hz or increments/revolution

-3-

2048 pulses/Hz or increments/revolution

-4-

4096 pulses/Hz or increments/revolution

ON-LINE

SH + PRG

66,
73

C027

Adjustment for
C025

For analog inputs:
1.000

-2.500...+2.500
(in steps of 0.001)

For digital frequency/incremental encoder inputs:
1.000

-5.000...+5.000
(in steps of 0.001)

ON-LINE

66,
73

C029

Auto-adjustm.
for feedback of
PI controller

-1-

Activate auto-adjustment

SH + PRG

75

C030*

Constant for
digital
frequency
output X9

-1-

512 pulses/Hz

-2-

1024 pulses/Hz

-3-

2048 pulses/Hz

-4-

4096 pulses/Hz

SH + PRG

90

C034

Master current -0-

0...20mA

-1-

4...20mA

SH + PRG

64

C036

Voltage for DC
injection
braking

0.0%

0...40%
(in steps of 0.1%)

ON-LINE

79

C038

Preselection:
JOG
frequency

-1-

JOG 1

-2-

JOG 2

...

...

-15-

JOG 15

SH + PRG

80

C039

Set-value for
C038

50.0Hz

-480...+480 Hz
(in steps of 0.1 Hz from 0.0 to 100 Hz
in steps of 1 Hz from 100 to 480 Hz)

ON-LINE

80

C040

Controller
enable

-0-

Controller inhibit

-1-

Controller enable

SH + PRG

58

C041

Direction of
rotation

-0-

Main set-value not changed

-1-

Main set-value inverted/invert

SH + PRG

58

C042

Quick stop

-0-

Quick stop not active/finish

-1-

Quick stop active/activate

SH + PRG

58

C043

TRIP reset
(only for
LECOM)

-0-

Reset fault

SH + PRG

117

C044*

Enable
process
control

-0-

Process control inhibited/finish

-1-

Process control enabled/start

SH + PRG

84,
94

C045

Enable JOG
frequency

-0-

Set-value 1 active/activate

-1-

JOG 1 active/activate

...

...

-15-

JOG 15 active/activate

SH + PRG

80

This manual is related to the following products: