Lenze 8615E User Manual
Page 71

69
Voltage boost V
min
In the low speed range, the obtained torque is determined largely
by the set voltage boost. If you set V
min
(C016), make sure that the
motor cannot be destroyed by overheat.
Experience tells that self-ventilated standard asynchronous
machines of insulation class B can be operated in a frequency
range up to 25Hz only for a short time with rated current. Therefore
proceed as follows:
•
The motor should be operated in idle running.
•
Provide a set-value of 4 to 5 Hz.
•
The voltage boost should be set such that
−
the motor current (C054) does not exceed the rated value
for short-time operation in the low frequency range.
−
the motor current (C054) does not exceed 80 % of its rated
value for permanent operation in the low frequency range.
For exact data of the permissible motor current please refer to the
motor manufacturer.
Forced-ventilated machines can be permanently operated with
rated current even in the low frequency range.
Code
Parameter
Meaning
Acceptance
C014
-0-
-1-
linear characteristic
square characteristic
[SH + PRG]
C015
50.0Hz
7.5...960Hz
V/f rated frequency
ON-LINE
C016
0.0%
0.0...40%
voltage boost
ON-LINE