3 technical data, 1 general data and operating conditions, Technical data – Lenze E94ASHE Axis Single Drive 32-104A User Manual
Page 56: General data and operating conditions, 3technical data

Technical data
General data and operating conditions
3
l
56
EDK94SH104 DE/EN/FR/ES/IT 5.1
3
Technical data
3.1
General data and operating conditions
Information on mains
Mains types
With earthed
*
point
Unrestricted use
IT systems
Observe instructions on specific measures!
Noise emission
EN 61800−3
Cable−guided, motor cable length up to 50 m: category C2
Noise immunity
EN 61800−3
Category C3
Conformity and approval
Conformity
CE
2006/95/EC
Low−voltage directive
Approval
UL
UL 508C
Power Conversion Equipment, File No. 132659
Protection of persons and devices
Enclosure
EN 60529
IP 20
Not in the wire range of
the terminals on the
motor side
NEMA 250
Protection against contact to
type 1
Insulation resistance
EN 61800−5−1
Overvoltage category III
Reduction from 2000 m amsl onwards: Overvoltage category
II
Insulation of control
circuits
EN 61800−5−1
Safe mains isolation by double/reinforced insulation.
Short−circuit strength
EN 61800−5−1
Motor connection: with restrictions, fault acknowledgement
required
Control connections: without restrictions
Motor protective
measures against
l
Short circuit
l
Earth fault
l
Overvoltage
l
Motor stalling
l
Motor overtemperature
(PTC or thermal contact, I
2
t monitoring)
Discharge current
EN 61800−5−1
> 3.5 mA AC, > 10 mA DC
Observe regulations and
safety instructions!
Cyclic mains switching
Cyclic mains switching of 5 times in 5 minutes is permissible
without restrictions.