Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17

75

7

Commissioning of the system

7.3

Detailed description of the commissioning steps

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.3.8

Determining the physical EtherCAT configuration (fieldbus scan)

In order to check the physical EtherCAT configuration, you can use »PLC Designer« to carry out a

fieldbus scan on the Lenze Controller online.

Preconditions
In order to execute a fieldbus scan, you must first configure the ...

Configuring the communication parameters

( 73)

and ...

• then use the menu command Online Login or + to log in on the Lenze Controller.

• For this, the PLC program must be error-free.
• By means of the log-in, the PLC program is loaded into the controller. In doing so, any existing

program is overwritten.

How to carry out a fieldbus scan with »PLC Designer«

1. Execute the Scan For Devices command in the context menu of the EtherCAT master.