4 error counters of the ethercat slaves, 1 error types "errors" and "forwarded errors, Error counters of the ethercat slaves ( 172) – Lenze EtherCAT Controller-based Automation User Manual
Page 172: 12 diagnostics
12
Diagnostics
12.4
Error counters of the EtherCAT slaves
172
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.4
Error counters of the EtherCAT slaves
The EtherCAT slaves have numerical error counters for detecting and analysing error states. All error
counters have a limited counting range of 0 ... 255. After the maximum value of 255 is reached, no
"wrap-around" takes place. If the PLC application is to make a sensible evaluation of the error
counters, these must be deleted by the application after the evaluation via a write access.
12.4.1
Error types "Errors" and "Forwarded Errors"
The EtherCAT slaves differ between errors detected in the slave for the first time (red error) and
forwarded errors, i.e. errors that have already been detected in a previous slave (green error).
When the corresponding error counters are evaluated, an error in the EtherCAT network can be
clearly assigned to a bus segment or a slave.
[12-1] Error types "Errors" and "Forwarded Errors"