12 diagnostics – Lenze EtherCAT Controller-based Automation User Manual
Page 194

12
Diagnostics
12.6
System error messages
194
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6245
...: Status change ’Operational’ takes some time ...
Information: The transition from "Safe-operational" ->
"Operational" takes longer. This message will be output after
10 s if one or several slaves did not change to the "Operational"
state. E.g. for Servo Drives 9400 with long cycle times, because
the standard device must synchronise with the communication
module (SYNC0).
6246
...: Status change ’Operational’ failed. Time-out.
The master cannot be set to "Operational" because of a time-out
(standard 55 s).
6247
...: Status change ’Operational’ failed. Slave error.
Setting the master to "Operational" failed due to a slave error.
Observe previous messages (slave error) in the logbook!
6248
...: Status change ’Operational’ cancelled by reset command.
The master cannot be set to "Operational" because the user
cancelled the procedure.
6250
...: Master stop failed (0x...).
The master cannot be stopped or cannot be set to the "Init"
state.
6251
...: Master stop failed (0x...). Slaves cannot be set to Pre-
operational.
The master cannot be stopped and slaves cannot be set to the
"Pre-operational" state.
6260
...: Master shutdown failed (0x...).
The master cannot be shut down and cannot be set to the "Init"
state.
6270
...: Remote API server start failed
Internal error: The remote API server cannot be started.
Communication of CoE parameters from the engineering tool
(»EASY Starter«/»Engineer«) is not possible.
6280
...: Start download
Information: Firmware/parameter set download was started.
6281
...: Download complete.
Information: Firmware/parameter set download was
completed.
Error no.
Message text in the Lenze Controller logbook
Description