beautypg.com

2 lenze controller logbook messages, Lenze controller logbook messages ( 190), Lenze controller logbook messages – Lenze EtherCAT Controller-based Automation User Manual

Page 190: 12 diagnostics, 6 system error messages 190

background image

12

Diagnostics

12.6

System error messages

190

Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

12.6.2

Lenze Controller logbook messages

Lenze Controller logbook messages are displayed in the »WebConfig« as errors (highlighted in red),

warnings, or information.
The same message text is displayed in the »PLC Designer« logbook and the EtherCAT logbook.

Logbook of the Lenze Controller in the »WebConfig«

( 170)

Note!

Cyclical messages as "WKC Error" or "Frame Lost" are displayed at the 1., 10., 100., 1000.,

10000. etc. occurrence.

Error no.

Message text in the Lenze Controller logbook

Description

5063

... (...): CoE 0x... : ... - invalid slave state

CAN over EtherCAT: CoE is only available from the "Pre-

Operational" state onwards. An attempt was made to access a

CoE slave parameter in the "Bootstrap" or "Init" state.

5064

... (...): CoE 0x... : ... - SDO abort ’Toggle bit unchanged

(0x05030000)’

The status of the toggle bit has not changed.

5065

... (...): CoE 0x... : ... - SDO abort ’Protocol timeout (0x05040000)’ SDO protocol time-out

5066

... (...): CoE 0x... : ... - SDO abort ’Client/server command specifier

invalid or unknown (0x05040001)’

Invalid or unknown specification symbol for the client/server

command

5067

... (...): CoE 0x... : ... - SDO abort ’Invalid block size (only block

mode) (0x05040002)’

Invalid block size (only in "Block mode")

5068

... (...): CoE 0x... : ... - SDO abort ’Invalid sequence number (only

block mode) (0x05040003)’

Invalid sequence number (only in "Block mode")

5069

... (...): CoE 0x... : ... - SDO abort ’CRC error (only block mode)

(0x05040004)’

CRC error (only in "Block mode")

5070

... (...): CoE 0x... : ... - SDO abort ’Memory overflow (0x05040005)’ Not enough space in the main memory

5071

... (...): CoE 0x... : ... - SDO abort ’Not supported access to object

(0x06010000)’

Access to object not supported

5072

... (...): CoE 0x... : ... - SDO abort ’Attempt to read a write-only

object (0x06010001)’

Read access to a write-only object

5073

... (...): CoE 0x... : ... - SDO abort ’Attempt to write to a read-only

object (0x06010002)’

Write access to a read-only object

5074

... (...): CoE 0x... : ... - SDO abort ’Object does not exist in the object

directory (0x06020000)’

An object does not exist in the object directory

5075

... (...): CoE 0x... : ... - SDO abort ’Object cannot be mapped to the

PDO (0x06040041)’

An object cannot be mapped into the PDO

5076

... (...): CoE 0x... : ... - SDO abort ’Number and length of the objects

to be mapped are greater than the PDO length (0x06040042)’

The number and/or length of the objects mapped would exceed

the PDO length

5077

... (...): CoE 0x... : ... - SDO abort ’General incompatibility of the

parameters (0x06040043)’

General parameter incompatibility

5078

... (...): CoE 0x... : ... - SDO abort ’General internal incompatibility

within the device (0x06040047)’

General internal device incompatibility

5079

... (...): CoE 0x... : ... - SDO abort ’Access failed due to a hardware

error (0x06060000)’

Access has failed due to a fault in the hardware

5080

... (...): CoE 0x... : ... - SDO abort ’Data format incompatible, length

of the service parameter incompatible (0x06070010)’

The data type or the parameter length does not correspond

5081

... (...): CoE 0x... : ... - SDO abort ’Data format incompatible, service

parameter too long (0x06070012)’

Incorrect data type (The parameter length is too large)

5082

... (...): CoE 0x... : ... - SDO abort ’Data format incompatible, service

parameter too short (0x06070013)’

Incorrect data type (The parameter length is too small)

5083

... (...): CoE 0x... : ... - SDO abort ’Subindex does not exist

(0x06090011)’

A subindex is not available

5084

... (...): CoE 0x... : ... - SDO abort ’Write access - parameter value

beyond the permissible range (0x06090030)’

The value range for parameters is too great (only for write

access)

5085

... (...): CoE 0x... : ... - SDO abort ’Write access - parameter value

too high (0x06090031)’

The parameter value is too high

5086

... (...): CoE 0x... : ... - SDO abort ’Write access - parameter value

too low (0x06090032)’

The parameter value is too low