2 lenze controller logbook messages, Lenze controller logbook messages ( 190), Lenze controller logbook messages – Lenze EtherCAT Controller-based Automation User Manual
Page 190: 12 diagnostics, 6 system error messages 190
12
Diagnostics
12.6
System error messages
190
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.6.2
Lenze Controller logbook messages
Lenze Controller logbook messages are displayed in the »WebConfig« as errors (highlighted in red),
warnings, or information.
The same message text is displayed in the »PLC Designer« logbook and the EtherCAT logbook.
Logbook of the Lenze Controller in the »WebConfig«
Note!
Cyclical messages as "WKC Error" or "Frame Lost" are displayed at the 1., 10., 100., 1000.,
10000. etc. occurrence.
Error no.
Message text in the Lenze Controller logbook
Description
5063
... (...): CoE 0x... : ... - invalid slave state
CAN over EtherCAT: CoE is only available from the "Pre-
Operational" state onwards. An attempt was made to access a
CoE slave parameter in the "Bootstrap" or "Init" state.
5064
... (...): CoE 0x... : ... - SDO abort ’Toggle bit unchanged
(0x05030000)’
The status of the toggle bit has not changed.
5065
... (...): CoE 0x... : ... - SDO abort ’Protocol timeout (0x05040000)’ SDO protocol time-out
5066
... (...): CoE 0x... : ... - SDO abort ’Client/server command specifier
invalid or unknown (0x05040001)’
Invalid or unknown specification symbol for the client/server
command
5067
... (...): CoE 0x... : ... - SDO abort ’Invalid block size (only block
mode) (0x05040002)’
Invalid block size (only in "Block mode")
5068
... (...): CoE 0x... : ... - SDO abort ’Invalid sequence number (only
block mode) (0x05040003)’
Invalid sequence number (only in "Block mode")
5069
... (...): CoE 0x... : ... - SDO abort ’CRC error (only block mode)
(0x05040004)’
CRC error (only in "Block mode")
5070
... (...): CoE 0x... : ... - SDO abort ’Memory overflow (0x05040005)’ Not enough space in the main memory
5071
... (...): CoE 0x... : ... - SDO abort ’Not supported access to object
(0x06010000)’
Access to object not supported
5072
... (...): CoE 0x... : ... - SDO abort ’Attempt to read a write-only
object (0x06010001)’
Read access to a write-only object
5073
... (...): CoE 0x... : ... - SDO abort ’Attempt to write to a read-only
object (0x06010002)’
Write access to a read-only object
5074
... (...): CoE 0x... : ... - SDO abort ’Object does not exist in the object
directory (0x06020000)’
An object does not exist in the object directory
5075
... (...): CoE 0x... : ... - SDO abort ’Object cannot be mapped to the
PDO (0x06040041)’
An object cannot be mapped into the PDO
5076
... (...): CoE 0x... : ... - SDO abort ’Number and length of the objects
to be mapped are greater than the PDO length (0x06040042)’
The number and/or length of the objects mapped would exceed
the PDO length
5077
... (...): CoE 0x... : ... - SDO abort ’General incompatibility of the
parameters (0x06040043)’
General parameter incompatibility
5078
... (...): CoE 0x... : ... - SDO abort ’General internal incompatibility
within the device (0x06040047)’
General internal device incompatibility
5079
... (...): CoE 0x... : ... - SDO abort ’Access failed due to a hardware
error (0x06060000)’
Access has failed due to a fault in the hardware
5080
... (...): CoE 0x... : ... - SDO abort ’Data format incompatible, length
of the service parameter incompatible (0x06070010)’
The data type or the parameter length does not correspond
5081
... (...): CoE 0x... : ... - SDO abort ’Data format incompatible, service
parameter too long (0x06070012)’
Incorrect data type (The parameter length is too large)
5082
... (...): CoE 0x... : ... - SDO abort ’Data format incompatible, service
parameter too short (0x06070013)’
Incorrect data type (The parameter length is too small)
5083
... (...): CoE 0x... : ... - SDO abort ’Subindex does not exist
(0x06090011)’
A subindex is not available
5084
... (...): CoE 0x... : ... - SDO abort ’Write access - parameter value
beyond the permissible range (0x06090030)’
The value range for parameters is too great (only for write
access)
5085
... (...): CoE 0x... : ... - SDO abort ’Write access - parameter value
too high (0x06090031)’
The parameter value is too high
5086
... (...): CoE 0x... : ... - SDO abort ’Write access - parameter value
too low (0x06090032)’
The parameter value is too low