_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5529
... (...): CoE receive WKC error. Command: ..., logic/physical
address: 0x..., WKC act/set=.../...
CAN over EtherCAT: Error during initialisation command for ’CoE
Receive Request’
One or several slaves have not processed a command.
5530
... (...): FoE receive WKC error. Command: ..., logic/physical
address: 0x..., WKC act/set=.../...
File over EtherCAT: Error during initialisation command for ’FoE
Receive Request’
One or several slaves have not processed a command.
5531
... (...): SoE receive WKC error. Command: ..., logic/physical
address: 0x..., WKC act/set=.../...
Sercos over EtherCAT: Error during initialisation command for
’SoE Receive Request’
One or several slaves have not processed a command.
5532
... (...): EoE send WKC error. Command: ..., logic/physical address:
0x..., WKC act/set=.../...
Ethernet over EtherCAT: Error during initialisation command for
’EoE Send Request’
One or several slaves have not processed a command.
5533
... (...): CoE send WKC error. Command: ..., logic/physical address:
0x..., WKC act/set=.../...
CAN over EtherCAT: Error during initialisation command for ’CoE
Send Request’
One or several slaves have not processed a command.
5534
... (...): FoE send WKC error. Command: ..., logic/physical address:
0x..., WKC act/set=.../...
File over EtherCAT: Error during initialisation command for ’FoE
Send Request’
One or several slaves have not processed a command.
5535
... (...): SoE send WKC error. Command: ..., logic/physical address:
0x..., WKC act/set=.../...
Sercos over EtherCAT: Error during initialisation command for
’SoE Send Request’
One or several slaves have not processed a command.
5541
... (...): Error at response to Init command - no response. State
change=’...’
Slave does not respond to Init command
5542
... (...): Error at response to Init command - validation error. State
change=’...’
Slave does not respond correctly to Init command
5543
... (...): Error at response to Init command - failed. State
change=’...’
Init command cannot be written to slave
5544
...: Error at response to master init command - no response. State
change=’...’
Slaves do not respond to Init command (broadcast)
5545
...: Error at response to master init command - validation error.
State change=’...’
Slaves do not respond correctly to Init command (broadcast)
5546
... (...): EtherCAT command ... is missing in the Ethernet frame.
Index of the missing command in the Ethernet frame=...
Internal error
5547
... (...): Mailbox init command timeout. Current state change of
the slave=’...’
Time-out during mailbox initialisation in the case of a state
change
5549
...: Ethernet cable is connected
Ethernet cable is connected again (link-up available)
5550
...:Ethernet cable is not connected
Ethernet cable is not connected (no link-up available)
5551
...: Timeout for cyclical commands. Time between transmission
processes too long
Internal error
5552
...: Redundant operation. Ethernet cable missing at the 2.
EtherCAT interface
Lenze controller does not support redundancy.
5554
... (...): Slaves signals error. AL status: '...' (0x...), AL status code: '...'
(0x...)
Slave indicates an error.
AL status and AL status code are slave-specific.
5555
... (...): Communication to device interrupted
Connection to slave is interrupted. The slave does not respond or
is no longer available.
5557
...: DC slaves ’in-sync’. Deviation ... ns
Information that the DC deviation is within the permissible
limits (standard 8 μs).
5558
...: DC slaves ’out-of-sync’. Deviation ... ns
Information that the DC deviation is not within the permissible
limits (standard 8 μs).
5562
...: Client registration lost
Internal error
5704
...: Connection was changed: connection is established
Internal information
5705
...: Connection was changed. Cookie: 0x... cause: ... (0x...)
Internal information
5706
...: Client was registered by cookie 0x... instance 0x... Id 0x...
result ...
Internal information
5707
...: Client was deleted by cookie 0x... instance 0x... Id 0x... result ... Internal information
5708
...: Unknown registration: 0x...
Internal error: Master outputs unknown message.
5719
... (...): Slave has incorrect status. Status set/act ’...’/’...’
Slave is not in expected status:
’req’ is the requested status and ’act’ the current status
5729
...: RAP - invalid parameter size for ...
Internal error
5730
...: RAP - Marshaling error. Cookie: 0x..., Command: 0x..., Cause:
... (0x...), Protocol Header: 0x...
Internal error
5731
...: ... could not be included in queue (missing calls of the
ProcessNotificationJobs)
Internal error
Error no.
Message text in the Lenze Controller logbook
Description