7.3.4.1

i700 parameter management in the Controller-based Automation system

Parameter download
The Servo-Inverter i700 itself does not store parameter settings safe against mains failure. All servo

inverter settings deviating from the Lenze standard setting are maintained centrally in the Lenze

Controller and stored there permanently (persistently). During the initialisation at run-up, only

these deviations are transferred to the servo inverter by the controller. Like this it is ensured that the

servo inverter works with the parameter settings provided for it.

Firmware download (optional)
The firmware of the Servo-Inverter i700 can – if so desired – be stored together with the »PLC

Designer« project. When the system is being powered up, the Lenze Controller then checks whether

the firmware version in the servo inverter matches the firmware version stored in the project for

this device. If this is not the case, the controller loads the firmware version stored in the project into

the servo inverter. In the event of a "Device replacement" service, it can thus be ensured that the

replacement device works with the same firmware version stored in the project for the original

device.