Dynaflow, User manual - maintenance, Error codes (cont.) – Ransburg DynaFlow User Manual User Manual
Page 70
LN-9400-00.9
DynaFlow
TM
User Manual - Maintenance
66
Displayed Text
Fault Cause
Corrective Action
Code
B010
(Cont.)
B020
B030
B040
B050
B060
RIO - Communi-
cations Error
(Cont.)
RIO - Invalid
BTW Type
RIO - Invalid
BTR Type
Gun/Channel
Number
RIO - Invalid
BTR Job
Number
RIO - Invalid
BTW Length
RIO cable is not properly
terminated at each end.
The PLC has issured a BTW with
an invalid BTW data type in the first
word offset.
The PLC has issued a BTW with an
invalid BTR data type in the second
word offset.
The PLC has issued a BTW with
an invalid gun or channel number
in the third word offset.
The PLC has issued a BTW with
an invalid job number in the fourth
word offset.
The PLC has issued a BTW with an
invalid message length (word count).
Check cable connections per Figure 25
of this manual.
Check each end of the cable to de-
termine if the terminating resistor is
installed at each end. The DynaFlow
system may not be the last rack on the
RIO cable. The value of the terminating
resistor is based on cable length, baud
rate, and if Extended Node Capability is
enabled at the PLC. If Extended Node
Capability is enabled, the terminating
resistors should always be 82 ohms.
Otherwise, the term-inating resistors
should be 150 ohms for 57.6 and 115.2
Kbaud and 82 ohms for 230.4 Kbaud.
In any case, use
1/2 watt resistors.
Have the PLC programmer reference
the "DynaFlow Programmer" manual
for the correct BTW data types.
Have the PLC programmer reference
the "DynaFlow Programmer" manual
for the correct BTR data types.
Have the PLC programmer ensure gun
and channel numbers are between 1 and
8, or 0 if not required for the particular
data type.
Have the PLC programmer ensure job
numbers are between 1 and 100, or 0 if
not required for the particular data type.
Have the PLC programmer reference
the "DynaFlow Programmer" manual
for the correct BTW message lengths.
ERROR CODES (Cont.)