Dynaflow, User manual - maintenance, Error codes (cont.) – Ransburg DynaFlow User Manual User Manual
Page 69

LN-9400-00.9
DynaFlow
TM
User Manual - Maintenance
65
Displayed Text
Fault Cause
Corrective Action
Non-Existent
Program -
GUN #<>
JOB # number entered for the indi-
cated GUN does not exist. JOB #
number defaulted to 00.
Last digit indicates
CHANNEL #.
Verify the following:
1. The JOB # has been saved in memory
for the indicated GUN.
2. The correct JOB # is being re-quest-
ed.
3. For discrete hard-wired JOB # select,
PROGRAM TOGGLE and JOB # inputs
have been asserted correctly by the PLC
or host computer.
Code
A011
A012
A013
A014
A015
A016
A017
A018
A021
A022
A023
A024
A025
A026
A027
A028
B001
B010
GUN Flow Out of
Range
System Halted
RIO - Communi-
cations Error
The total flow rate for GUN # has
exceeded the MAXIMUM FLOW
RATE JOB parameter or fallen below
the MINIMUM FLOW RATE JOB
parameter. For Manual GUNs only.
System Ready/Halt input is
inactive.
PLC and DynaFlow are not set to
the same:
- baud rate
- rack address
- rack size
- rack starting quarter
RIO cable is not connected to the
proper terminals at either end.
See "Flow Too Low" and "Flow Too
High" faults.
This input is typically used as an interlock
to other control equipment or it is simply
hard-wired to 24 VDC. Supply 24 VDC
to the System Ready/Halt input.
Check with the PLC programmer to de-
termine the correct values for baud rate,
rack address, rack size, and rack start-
ing quarter and then set the DynaFlow
Interface Module DIP SW1 and SW2 to
the appropriate settings per "Interface
Module DIP SW2 Settings" and "Mother
Board Signal ID (J3, J4, J5, J6 Channel
Cards" respect-ively in this section.
Check cable connections per Figure 25
ERROR CODES (Cont.)