beautypg.com

Block-transfer sequence with status bits, Block-transfer sequence with status bits -17 – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

Page 89

background image

Publication 1785-UM012D-EN-P - July 2005

Communicating with Remote I/O 6-17

Block-Transfer Sequence
with Status Bits

The following figure describes the different states of the block-transfer
status bits.

bit and starts the watchdog timer.

I/O scanner

ladder logic

The processor sends the block-transfer
request to the I/O scanner, sets the .EW bit,
and resumes the program scan.

Transfers the block-transfer
request to/from the I/O chassis.

Start

Detects that a rung containing a
block-transfer is enabled and sets the
enable .EN bit and resets the .ST, .DN, .ER,
and .EW status bits.

Does the module respond?

yes

B

no

C

see page
6-19

The scanner accesses the BTW file in the data
table and copies the data to the active buffer.

Is an active buffer available?

Executes block-transfer
asynchronously to the
program scan

Does this slot address
have a BT in process?

no

yes

The scanner place the request
in the waiting queue.

A

Is the request a BTW?

yes

no

yes

no

see page 6-18

The scanner sets the .ST status