S:11 – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
Page 278

Publication 1785-UM012D-EN-P - July 2005
B-4 Processor Status File
S:11
This Word
Stores
S:11major fault word
S:11/00
Corrupted program file (codes 10-19). See major fault codes (S:12).
S:11/01
Corrupted address in ladder program (codes 20-29). See major
fault codes (S:12).
S:11/02
Programming error (codes 30-49). See major fault codes (S:12).
S:11/03
Controller detected an SFC fault (codes (71-79). See major fault
codes (S:12).
S:11/04
Controller detected an error when assembling a ladder program
file (code 70); duplicate LBLs found.
S:11/05
Start-up protection fault. The controller sets this major fault bit
when powering up in Run mode if the user control bit S:26/1 is set.
S:11/06
Peripheral device fault
S:11/07
User-generated fault; controller jumped to fault routine (codes
0-9). See major fault codes (S:12).
S:11/08
Watchdog faulted
S:11/09
System configured wrong (codes 80-82, 84-88, 200-208). See
major fault codes (S:12).
S:11/10
Recoverable hardware error
S:11/11
MCP does not exist or is not a ladder or SFC file
S:11/12
PII file does not exist or is not a ladder file
S:11/13
STI file does not exist or is not a ladder file
S:11/14
Fault routine does not exist or is not a ladder file
S:11/15
Faulted program file does not contain ladder logic