Valid formats for addressing data files are:
For more information about entering addresses, see the documentation for
your programming software.
Specifying I/O Image Addresses
The I/O image address corresponds to the physical location of the I/O circuit
in the I/O chassis:
If You Want to Access
Use this Addressing Format
And See Page
Input or output bit in the I/O image table
I/O image address
Bit, word, sub-member, data block, file, or I/O image bit
Logical address
A component within a logical address by substituting the
value in another address
Indirect address
An address offset by some number of elements
Indexed address
A substitute name for an address
Symbolic address
a
I/O address identifierI = input device
O = output device
bb
I/O Rack numberPLC-5/11, -5/20, -5/20E00-03 (octal)
PLC-5/3000-07 (octal)
PLC-5/40, -5/40L, -5/40E00-17 (octal)
PLC-5/60, -5/60L, -5/80, -5/80E00-27 (octal)
c
I/O Group number0-7 (octal)
dd
Terminal (bit) number00-17 (octal)
To Specify this
Address
Example
Input Image Bit
Output Image Bit
I for input
2-digit I/O rack Number
I/O group number (0-7)
Input number (0-7, 10-17)
I
:
0
1
7
/
0
1
O for output
2-digit I/O rack Number
I/O group number (0-7)
Output number (0-7, 10-17)
O
:
0
1
7
/
0