Remote i/o system, Ethernet transmit led – Rockwell Automation 1785-Lxxx Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
Page 354
Publication 1785-UM012D-EN-P - July 2005
F-6 Troubleshooting
Ethernet Transmit LED
The PLC-5 Ethernet interface contains an Ethernet Transmit LED that lights
(green) briefly when the Ethernet port is transmitting a packet. It does not
indicate whether or not the Ethernet port is receiving a packet.
Remote I/O System
Troubleshooting Guide for the 1771-ASB Series C and D
Adapter Module
BATT
PROC
FORCE
COMM
PROG
RUN
R
E
M
ENET
TRANSMIT
ACTIVE
ADAPTER
FAULT
I/O RACK
FAULT
Indicators
Description
Probable Cause
Recommended Action
Active
Adapter
Fault
I/O
Rack
On
Off
Off
Normal indication;
remote adapter is fully
operational
Off
On
Off
RAM memory fault, watchdog timeout Replace module.
On
Blink
Off
Module placement error I/O module in incorrect slot.
Place module in correct slot in chassis.
Blink in unison
Off
Incorrect starting I/O
group number
Error in starting I/O group number or
I/O rack address
Check switch settings.
On
On
On
Module not
communicating
Incorrect transmission rate setting
Off
On
On
Module not
communicating
Scan switch set for “all but last four
slots” in 1/4 rack
Reset scan switch setting.
Blink
Off
Off
Remote adapter not
actively controlling I/O
(scanner to adapter
communication link is
normal)
(1)
Controller is in program or test mode
Scanner is holding adapter module in
fault mode
Fault should be cleared by I/O scanner.
LEDs sequence on/off from
top to bottom
Module not
communicating
Another remote I/O adapter with the
same address is on the link.
Correct the address.