Placing System Hardware
Using This Chapter
Determining the Proper
Environment
Place the controller in an environment with conditions that fall within these
guidelines:
Separate your programmable controller system from other equipment and
plant walls to allow for convection cooling. Convection cooling draws a
vertical column of air upward over the controller. This cooling air must not
exceed 60° C (140° F) at any point immediately below the controller. If the air
temperature exceeds 60° C, install fans that bring in filtered air or recirculate
internal air inside the enclosure, or install air-conditioning/heat-exchanger
units.
To allow for proper convection cooling in enclosures containing a
controller-resident chassis and remote I/O chassis, follow these guidelines.
For Information About
Go to Page
Determining the proper environment
Protecting your controller
Avoiding electrostatic damage
Laying out your cable raceway
Laying out your backpanel spacing
Grounding your system
Environmental Condition Acceptable Range
Operating temperature
0 to 60° C (32 to 140° F)
Storage temperature
-40 to 85° C (-40 to 185° F)
Relative humidity
5 to 95% (without condensation)