P545 actual bus value 3, P546 digital bus setpoint 1, P546 – NORD Drivesystems BU0060 User Manual
Page 84: Digital bus setpoint

CANopen – Supplementary manual options for NORD - Frequency Inverters
84
BU 0060 GB-4112
P545
Actual bus value 3
(Actual bus value 3)
S
P
0 ... 24
{ 0 }
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
Pos : 155 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P546 – Funkti on Bus-Soll wert 1 [ SK 500... 535E] @ 0\ mod_1328097962990_388. doc x @ 11916 @ @ 1
P546
Digital Bus setpoint 1
(Function of bus setpoint 1)
S
P
0 ... 55
{ 1 }
In this parameter, a function is allocated to the output setpoint 1 during bus actuation.
The possible analog functions can be found in the following table.
NOTE:
For further details please refer to the manual for the frequency inverter (P400, P546),
the relevant BUS operating instructions or the manuals BU 0510 / BU0550.
Pos : 156 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P546 – Funkti on Bus-Soll wert e [SK 54xE] @ 0\mod_1328098077630_388. doc x @ 11939 @ @ 1
P546
[-01]
...
[-05]
Digital Bus setpoint
(Function of bus setpoint)
S
P
0 ... 57
{ [-01] = 1 }
all other { 0 }
In this parameter, during bus actuation a function is allocated to the setpoint provided.
NOTE:
The setpoints 4 and 5 must be supported by the relevant bus module. For further
details please refer to the manual for the frequency inverter (P400, P546), the
relevant BUS operating instructions or the manuals BU 0510 / BU0550.
[-01] = Bus setpoint 1
[-02] = Bus setpoint 2
[-03] = Bus setpoint 3
[-04] = Bus setpoint 4
[-05] = Bus setpoint 5
0 =
Off
16 = Process controller lead
1 =
Setpoint frequency
17 = BusIO In Bits 0...7
2 =
Torque current limit (P112)
18 = Curve travel calculator
3 =
Actual frequency PID
19 = Set relays, "Output status"
(P434/441/450/455=38)
4 =
Frequency addition
20 = Set analog output (P418=31)
5 =
Frequency subtraction
21 = ... 45 reserved from SK 530E and above
à
BU 0510
6 =
Current limit (P536)
46 = Setpoint Torque processreg., "Setpoint
torque process controller"
7 =
Maximum frequency (P105)
47 = reserved from SK 530E and above
à
BU 0510
8 =
Actual PID frequency limited
48 = Motor temperature (SK 540E and above)
9 =
Actual PID frequency monitored
49 = reserved from SK 540E and above
à
BU 0510
10 = Torque servo mode (P300)
53 = d-correction F process (SK 540E and
above)
11 = Torque precontrol (P214)
54 = d-correction Torque (SK 540E and above)
12 = Reserved
55 = d-correction F+torque (SK 540E and
above)
13 = Multiplication
56 = reserved from SK 540E and above
à
BU 0510
14 = Process controller actual value
57 = reserved from SK 540E and above
à
BU 0510
15 = Process controller setpoint
Pos : 157 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P547 – Funkti on Bus-Soll wert 2 [ SK 500... 535E] @ 0\ mod_1328098180008_388. doc x @ 11962 @ @ 1