beautypg.com

P546 bus setpoint 1, P547 bus setpoint 2, P548 bus setpoint 3 – NORD Drivesystems BU0060 User Manual

Page 74

background image

CANopen – Supplementary manual options for NORD - Frequency Inverters

74

BU 0060 GB-4112

P546

Bus setpoint 1

(Bus setpoint 1)

SK 300E /

SK 7x0E

S

P

0 ... 7

{ 1 }

In this parameter, a function is allocated to the output setpoint 1 during bus actuation. The
settings 2 to 6 are only relevant for type SK 700E and SK 750E inverters in combination with the
POSICON option.

0 = Off

1 = Setpoint frequency (16 bit)

2 = 16 Bit setpoint position

3 = 32 Bit Bit setpoint position (PPO

type 2 or 4)

4 = POSICON control terminals (16 Bit)

3

5 = Setpoint position (16 Bit)

6 = Setpoint position (32 Bit) increment

7 = Bus I/O In Bits 0-7

Pos : 126 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P547 – Bus-Sollwert 2 [SK 300E, SK 7x0E] @ 1\ mod_1335788467112_388. doc x @ 24976 @ @ 1

P547

Bus setpoint 2

(Bus setpoint 2)

SK 300E /

SK 7x0E

S

P

0 ... 20

{ 0 }

In this parameter, a function is allocated to the setpoint 2 which is output during bus actuation.

0 = Off

11 = Torque precontrol (only SK 7x0E)

(P214)

1 = Setpoint frequency

12 = POSICON control terminals (only

SK 7x0E)

2 = Torque current limit (P112)

13 = Multiplication (only SK 7x0E)

3 = Actual frequency PID

14 = Process controller actual value

4 = Frequency addition

15 = Process controller setpoint

5 = Frequency subtraction

16 = Process controller lead

6 = Current limit (only SK 7x0E) (P536)

17 = BusIO In Bits 0...7

7 = Maximum frequency (only SK 7x0E)

(P105)

18 = Curve travel calculator (only

SK 7x0E)

8 = Actual PID frequency limited

19 = Set relays (P541)

9 = Actual PID frequency monitored

20 =

Set analog output (P542)

10 =

Torque

Pos : 127 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P548 – Bus-Sollwert 3 [SK 300E, SK 7x0E] @ 1\ mod_1335790742656_388. doc x @ 25000 @ @ 1

P548

Bus setpoint 3

(Bus setpoint 3)

SK 300E /

SK 7x0E

S

P

0 ... 20

{ 0 }

In this parameter, a function is assigned to the delivered setpoint 3 (SW3) for bus control. This is

identical to parameter P547 and is only present if P546 ≠ 3 and 6.

Pos : 128 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P551 – Antriebs profil @ 0\ mod_1328098517139_388. doc x @ 12054 @ @ 1

3

The "reference run", "teach-in" and "reset position can be controlled via the other bits:

Bit 0: Pos. array / Pos. increment

Bit 1: Pos. array / Pos. increment

Bit 2: Pos. array / Pos. increment

Bit 3: Pos. array / Pos. increment

Bit 4: Pos. array / Pos. increment

Bit 5: Pos. array / Pos. increment

Bit 6: Approach reference point

Bit 7: Ref. point

Bit 8: Teach- In

Bit 9: Quit Teach- In

Bit 10: Reset pos.