P741, Process data bus out, P745 module version – NORD Drivesystems BU0060 User Manual
Page 76: P745, Module version, P746 module status

CANopen – Supplementary manual options for NORD - Frequency Inverters
76
BU 0060 GB-4112
P741
[-01]
...
[-06]
Process data Bus Out
(Process data bus out)
SK 300E /
SK 7x0E
S
0000 ... FFFF (hex)
This parameter provides
information about the actual
status word and the actual
values that are transferred
via the bus systems.
Series SK 300E
[-01] = Status word
Series SK 7x0E
[-01] = Status word
[-02] = Actual value 1
[-03] = Actual value 2
[-04] = Actual value 3
[-02] = Actual value 1
[-03] = Actual val. 1 High byte
[-04] = Actual value 2
[-05] = Actual value 3
[-05] = Bus I/O Out Bit (P481)
[-06] = Bus I/O Out Bit (P481)
Pos : 133 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P745 – Baugruppen Versi on [ SK 300E] @ 1\ mod_1335791798489_388. doc x @ 25072 @ @ 1
P745
Module version
(Module version)
SK 300E
0.0 ... 3276.7
Version status (software version) of the technology unit (SK TU2-xxx), but only when own
processor is present, i.e. not for SK TU2-CTR.
Have this data available if you have a technical query.
Pos : 134 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P745 – Baugruppen Versi on [ SK 7x0E] @ 1\ mod_1335792003777_388.doc x @ 25096 @ @ 1
P745
[-01]
...
[-03]
Module version
(Module version)
SK 7x0E
S
0000 ... FFFF (hex)
Version status (software version) of the installed option
module(s) but only when own processor is present, i.e. not for
SK TU1-CTR.
Have this data available if you have a technical query.
[-01] = Technology unit
[-02] = Customer unit
[-03] = Special extension unit
Pos : 135 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P746 – Baugruppen Z ust and [SK 300E] @ 1\ mod_1335792492116_388. doc x @ 25120 @ @ 1
P746
Module status
(Module status)
SK 300E
S
0000 ... FFFF (hex)
Shows the actual status (readiness, error, communication) of the technology unit (SK TU2-xxx),
but only when own processor is present, i.e. not for SK TU2-CTR.
Example:
0603
hex
High byte = 06
hex
à Profibus
Low byte = 03
hex
à Module ready + connection to master
Details of the codes specific to the bus can be found in the section "Error monitoring" of the
relevant supplementary instructions.
Pos : 136 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P746 – Baugruppen Z ust and [SK 7x0E] @ 1\ mod_1335792880284_388.doc x @ 25144 @ @ 1