5 parameters, P543 actual bus value 1, P543 – NORD Drivesystems BU0060 User Manual
Page 83: Bus actual value, P544 actual bus value 2

5 Parameters
BU 0060 GB-4112
83
P543
Actual bus value 1
(Actual bus value 3)
S
P
0 ... 24
{ 1 }
The return value 1 can be selected for bus actuation in this parameter.
The possible analog functions can be found in the following table.
NOTE:
For further details please refer to the manual for the frequency inverter (P418, P543),
the relevant BUS operating instructions or BU 0510.
Pos : 152 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P543 – Bus-Ist wert e [ SK 54xE] @ 0\ mod_1328097636349_388. doc x @ 11847 @ @ 1
P543
[-01]
...
[-05]
Bus actual value
(Bus – Actual value)
S
P
0 ... 57
{ [-01] = 1 }
{ [-02] = 4 }
{ [-03] = 9 }
{ [-04] = 0 }
{ [-05] = 0 }
In this parameter the return value for bus actuation can be selected.
NOTE:
The actual values 4 and 5 must be supported by the relevant bus module. For
further details please refer to the manual for the frequency inverter (P418, P543),
the relevant BUS operating instructions or the manuals BU 0510 / BU0550.
[-01] = Bus - Actual value 1
[-02] = Bus - Actual value 2
[-03] = Bus - Actual value 3
[-04] = Bus - Actual value 4
[-05] = Bus - Actual value 5
0 =
Off
13 = ... 16 Reserved
1 =
Actual frequency
17 = Value analog input 1
2 =
Actual speed
18 = Value analog input 2
3 =
Current
19 = Setpoint frequency master
value(P503)
4 =
Torque current (100% = P112)
20 = Setpoint frequency master value after
ramp "Setpoint frequency master
value after ramp"
5 =
Digital IO status
21 = Act. freq. without slip master value
"Actual frequency without slip master
value"
6 =
... 7 Reserved
22 = Speed encoder
(only possible with
SK 520E and encoder feedback)
8 =
Setpoint frequency
23 = Actual frequency with slip, "Actual
frequency with slip"
(SW V2.0 and above)
9 =
Error number
24 = Master value, actual freq. with slip,
"Master value, actual freq. with slip"
(SW V2.0 and above)
10 = ... 11 Reserved
53 = ... 57 Reserved
12 = BusIO Out Bits 0...7
Pos : 153 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P544 – Bus-Ist wert 2 [SK 500. .. 535E] @ 0\ mod_1328097766412_388.doc x @ 11870 @ @ 1
P544
Actual bus value 2
(Actual bus value 2)
S
P
0 ... 24
{ 0 }
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
Pos : 154 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P500-P599/ Paramet er P545 – Bus-Ist wert 3 [SK 500. .. 535E] @ 0\ mod_1328097880052_388.doc x @ 11893 @ @ 1
4
The assignment of the digital inputs in P543/ 544/ 545 = 5
Bit 0 = DigIn 1
Bit 1 = DigIn 2
Bit 2 = DigIn 3
Bit 3 = DigIn 4
Bit 4 = DigIn 5
Bit 5 = DigIn 6 (SK 520E and above)
Bit 6 = DigIn 7 (SK 520E and above)
Bit 7 = Dig. func. AIN1
Bit 8 = Dig. func. AIN1 AIN2
Bit 9 = DigIn 8 (SK 540E and above)
Bit 10 = DigIn 1, 1.IOE (SK 540E and above)
Bit 11 = DigIn 2, 1.IOE (SK 540E and above)
Bit 12 = Out 1/ MFR1
Bit 13 = Out 2/ MFR2
Bit 14 = Out 3/ DOUT1 (SK 520E and above)
Bit 15 = Out 4/ DOUT2 (SK 520E and above)