3 information, Information, 5 parameters – NORD Drivesystems BU0060 User Manual
Page 75: P551 drive profile, P707, Software-version, P740, Process data bus in

5 Parameters
BU 0060 GB-4112
75
P551
Drive profile
(Drive profile)
S
0 … 1
{ 0 }
According to the option the relevant process data profiles can be activated with this parameter.
Note
Activation of profiles
This parameter is only effective for pluggable technology modules (SK TU3-…).
System
CANopen
DeviceNet
InterBus
Technology module
SK TUx-CAO
SK TUx-DEV
SK TUx-IBS
Setting
0 = OFF =
USS protocol (Profile "Nord")
1 = ON =
DS402 profile
AC Drives profile
Drivecom profile
Pos : 129 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ P7xx I nf or mationen @ 0\ mod_1328170311705_388. doc x @ 12293 @ 5 @ 1
5.1.3 Information
Parameter
Setting value / Description / Note
Supervisor
Parameter set
Pos : 130 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P707 – Soft ware- Versi on/-Revisi on @ 0\ mod_1328171743458_388. doc x @ 12479 @ @ 1
P707
[-01]
...
[-03]
Software-Version
(Software version/ revision)
0.0 ... 9999.9
This parameter shows the software and revision
numbers in the FI. This can be significant when
different FIs are assigned the same settings.
Array 03 provides information about any special
versions of the hardware or software A zero
stands for the standard version.
... [-01] = Version number (1.7)
... [-02] = Revision number (R0)
... [-03] = Special version of hard-/software (0.0)
Pos : 131 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P740 – Prozes sdat en Bus In [ SK 300E, SK 7x0E] @ 1\ mod_1335791131327_388. doc x @ 25024 @ @ 1
P740
[-01]
...
[-06]
Process data Bus In
(Process data bus in)
SK 300E /
SK 7x0E
S
0000 ... FFFF (hex)
This parameter informs
about the actual control
word and the setpoints that
are transferred via the bus
systems.
For display, a BUS system
must be selected in P509
Series SK 300E:
[-01 ] = Control word
Series SK 7x0E:
[-01 ] = Control word
[-02] = setpoint value 1
[-03] = setpoint value 2
[-04] = setpoint value 3
[-02] = setpoint value 1
[-03] = Setpoint val. 1 High byte
[-04] = setpoint value 2
[-05] = setpoint value 3
[-05] = Bus I/O In Bits (P480)
[-06] = Bus I/O In Bits (P480)
Pos : 132 /Anleit ungen/5. / 6. Parametrier ung [BU 0500 / BU 0200]/ Par ameter/ P700-P799/ Paramet er P741 – Prozes sdat en Bus Out [ SK 300E / SK 7x0E] @ 1\ mod_1335791437905_388. doc x @ 25048 @ @ 1