4 Communication and Protocol

BU 0060 GB-4112

63

Changing the COB-ID (address) of a PDO

Changes to the identifier of a PDO can only be made when the NMT status machine of the inverter is
in the "Pre-Operational" state.

Each Transmit and Receive PDO has its own parameter for this setting.

PDO

Receive PDO

Send PDO

PDO 1

0x1400 Sub 1

0x1800 Sub 1

PDO 2

0x1401 Sub 1

0x1801 Sub 1

PDO 3

0x1402 Sub 1

0x1802 Sub 1

PDO 4

0x1403 Sub 1

0x1803 Sub 1

Table 20: Index table for transmit and receive PDOs of the inverter

The following parameter is a 32 bit value, which includes other information in addition to the identifier.

Bit number

Value

Meaning

31

0

PDO is active

1

PDO is switched off

30

1

Values cannot be changed

29 to 11

0

10 to 0

X

PDO identifier ( COB – ID )

Table 21: Description of PDO COB-ID entry

The PDO identifier is stored in bits 0 to 10. The bit 31 must be set to null, otherwise the PDO will be
deactivated. If, e.g. the identifier for a transmit PDO is changed to 0x201, the value 0x40000201 must
be entered in the appropriate parameter.

The new identifier becomes valid by setting the NMT status machine to the "Operational" state.