4 Communication and Protocol
BU 0060 GB-4112
51
Figure 9: Sequence of data transfer
Pos : 80 /Anl eitungen/ Elektroni k/ Bus s yst eme/4. Kommuni kati on und Prot okoll + Proz ess datentr ans fer /CAN open [ BU 0060]/D as C ANnord Pr ot okoll /Broadc ast- T elegramme [CAN] @ 1\ mod_1342083279128_388. doc x @ 31952 @ 3 @ 1
4.2.5 Broadcast telegrams
To control several frequency inverters simultaneously (e.g. same enable and same setpoint), it is
possible to address frequency inverter groups or all frequency inverters using broadcast telegrams.
This means that, in addition to the identifiers described above, additional broadcast identifiers for each
frequency inverter are also valid. A range of 32 addresses is assigned to one broadcast identifier. All
connected frequency inverters can be controlled using the broadcast identifier 1032.
CAN address (P515)
Broadcast identifier
00 - 31
1024 (400h)
32 - 63
1025 (401h)
64 - 95
1026 (402h)
96 - 127
1027 (403h)
128 - 159
1028 (404h)
160 - 191
1029 (405h)
192 - 223
1030 (406h)
224 - 255
1031 (407h)
0 - 255
1032 (408h)
Table 12: Assignment of CAN address (P515) to the broadcast identifier