background image

CANopen – Supplementary manual options for NORD - Frequency Inverters

42

BU 0060 GB-4112

4.1.4 Frequency inverter status machine

The frequency inverter passes through a status machine. The changes between various states are
triggered by the respective control commands in the process data control word. The actual status is
returned in the process data status word.

After switching on, the inverter is in switch-on disabled status. This status can only be ended by
transmitting the “Shut down (Off 1)” command.

The answer to a master telegram normally does not yet contain a reaction to the control command.
The controller must check the answers from the slaves as to whether the control command has been
carried out.

The following bits indicate the status of the frequency inverter:

Status

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Switch-on

disable

Emergency

stop

Disable

voltage

Fault

Operation

enabled

Standby

Ready for

switch-on

Not ready to start

0

X

X

0

0

0

0

Starting disabled

1

X

X

0

0

0

0

Ready to start

0

1

1

0

0

0

1

Activated

0

1

1

0

0

1

1

Operation enabled

0

1

1

0

1

1

1

Fault

0

X

X

1

0

0

0

Error active

0

X

X

1

1

1

1

Emergency stop

active

0

0

1

0

1

1

1