beautypg.com

Electrical connections – KROHNE OPTISONIC 3400 EN User Manual

Page 52

background image

4

ELECTRICAL CONNECTIONS

52

OPTISONIC 3400

www.krohne.com

11/2013 - 4002037702 - HB OPTISONIC 3400 -en-R02

Pulse and frequency output passive P

N

NAMUR, Ex i I/Os

• Connection acc. to EN 60947-5-6
• open:

I

nom

= 0.43 mA

closed:
I

nom

= 4.5 mA

• X designates the connection terminals B or D, depending on the version of the signal

converter.

Control input passive, Ex i I/Os

• 5.5 V ≤ U

ext

≤ 32 VDC

• I

max

= 6 mA at U

ext

≤ 24 V

I

max

= 6.5 mA at U

ext

≤ 32 V

• Switching point for identifying "contact open or closed":

Contact open (off): U

0

≤ 3.5 V with I ≤ 0.5 mA

Contact closed (on): U

0

≥ 5.5 V with I ≥ 4 mA

• X designates the connection terminals B, if available.

Figure 4-25: Pulse and frequency output passive P

N

as per NAMUR EN 60947-5-6 Exi

INFORMATION!

Any connection polarity.

Figure 4-26: Control input passive C

p

Exi

1 Signal