Technical data – KROHNE OPTISONIC 3400 EN User Manual
Page 102
8
TECHNICAL DATA
102
OPTISONIC 3400
www.krohne.com
11/2013 - 4002037702 - HB OPTISONIC 3400 -en-R02
Control input
Control input
Control input
Control input
Function
Hold value of the outputs (e.g. for cleaning work), set value of the
outputs to "zero", counter and error reset, stop counter, range
conversion, zero calibration
Start of dosing when dosing function is activated.
Operating data
Basic I/Os
Modular I/Os
Ex i
Active
-
U
int
= 24 VDC
Terminals open:
U
0, nom
= 22 V
Terminals bridged:
I
nom
= 4 mA
On:
U
0
≥ 12 V with
I
nom
= 1.9 mA
Off:
U
0
≤ 10 V with
I
nom
= 1.9 mA
-
Passive
U
ext
≤ 32 VDC
I
max
= 6.5 mA at
U
ext
≤ 24 VDC
I
max
= 8.2 mA at
U
ext
≤ 32 VDC
Contact closed (On):
U
0
≥ 8 V with
I
nom
= 2.8 mA
Contact open (Off):
U
0
≤ 2.5 V with
I
nom
= 0.4 mA
U
ext
≤ 32 VDC
I
max
= 9.5 mA at
U
ext
≤ 24 V
I
max
= 9.5 mA at
U
ext
≤ 32 V
Contact closed (On):
U
0
≥ 3 V with
I
nom
= 1.9 mA
Contact open (Off):
U
0
≤ 2.5 V with
I
nom
= 1.9 mA
U
ext
≤ 32 VDC
I ≤ 6 mA at
U
ext
= 24 V
I ≤ 6.6 mA at
U
ext
= 32 V
On:
U
0
≥ 5.5 V or
I ≥ 4mA
Off:
U
0
≤ 3.5 V or
I ≤ 0.5 mA
U
i
= 30 V
I
i
= 100 mA
P
i
= 1 W
C
i
= 10 nF
L
i
= 0 mH
NAMUR
-
Active to
EN 60947-5-6
Contact open:
U
0, nom
= 8.7 V
Contact closed (On):
I
nom
= 7.8 mA
Contact open (off):
U
0, nom
= 6.3 V with
I
nom
= 1.9 mA
Identification for
open terminals:
U
0
≥ 8.1 V with
I ≤ 0.1 mA
Identification for
short circuited
terminals:
U
0
≤ 1.2 V with
I ≥ 6.7 mA
-