TECHNICAL DATA
8
103
OPTISONIC 3400
www.krohne.com
11/2013 - 4002037702 - HB OPTISONIC 3400 -en-R02
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
Description
Galvanically isolated acc. to IEC 61158
Profile version: 3.02
Current consumption: 10.5 mA
Permissible bus voltage: 9...32 V; in Ex application 9...24 V
Bus interface with integrated reverse polarity protection
Typical error current FDE (Fault Disconnection Electronic): 4.3
mA
Bus address adjustable via local display on the measuring
device
Function blocks
6 x analogue input, 3 x totaliser
Output data
Volume flow, mass flow, velocity of sound, flow speed, gain,
SNR, electronic temperature, power supply
(Further meas. values and diagnostic data is available via acyclic
access)
FOUNDATION Fieldbus
FOUNDATION Fieldbus
FOUNDATION Fieldbus
FOUNDATION Fieldbus
Description
Galvanically isolated acc. to IEC 61158
Current consumption: 10.5 mA
Permissible bus voltage: 9...32 V; in Ex application 9...24 V
Bus interface with integrated reverse polarity protection
Link Master function (LM) supported
Tested with Interoperable Test Kit (ITK) version 6.0
Function blocks
1 x analogue input, 2 x integrator, 1 x PID
Output data
Volume flow, mass flow, flow speed, electronic temperature,
velocity of sound, gain, SNR
Diagnostic data
MODBUS
MODBUS
MODBUS
MODBUS
Description
Modbus RTU, Master / Slave, RS485
Address range
1…247
Supported function codes
01, 02, 03, 04, 05, 08, 16, 43
Supported Baudrate
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Baud