Cas200 current inputs, Cas200 current inputs 83, Figure 5.6— cas200 input circuit 83 – Watlow CAS200 User Manual
Page 95
CAS200 User’s Guide
Chapter 5: Troubleshooting and Reconfiguring
Watlow Anafaze
83
Figure 5.6 shows the schematic for one single-ended sensor
input to the CAS200. See CAS200 Current Inputs on page
83 and CAS200 Voltage Inputs on page 84 for specific
instructions and resistor values for voltage and current
inputs.
Figure 5.6
CAS200 Input Circuit
CAS200 Current Inputs
For each current input on a CAS200 scanner, you must
install one resistor. The value of the resistor must be
correct for the expected input range. Install the resistor in
the listed resistor location.
Table 5.3
Resistor Values for CAS200
Current Inputs
Resistor tolerance:
±
0.1%
Input Range
Resistor Value RD
0 - 10mA
6.0
Ω
0 - 20mA
3.0
Ω
IN +
RD
Analog
Input
Terminals
RC
Com
To CAS200
Circuitry
(Voltage only)
(Voltage and Current)
Measurement
- 12LS Controller (111 pages)
- 8LS Controller (140 pages)
- 8PID Controller (55 pages)
- Addendum to EZwarePlus (50 pages)
- ANASCAN (62 pages)
- ANASOFT (95 pages)
- ANAWIN 2 (154 pages)
- ANAWIN 3 (23 pages)
- Calibrating Watlow Series 988 Family Process Controls (19 pages)
- CAS (98 pages)
- CLS (180 pages)
- CLS200 (251 pages)
- CLS200, MLS300 and CAS200 (92 pages)
- Control Console (12 pages)
- CPC400 (230 pages)
- DIN-A-MITE Style A (9 pages)
- DIN-A-MITE Style B (14 pages)
- DIN-A-MITE Style C (22 pages)
- DIN-A-MITE Style D (9 pages)
- DIN-Mount Adapter Instruction Sheet, Rev A (1 page)
- Dual DAC (4 pages)
- EM Gateway (28 pages)
- E-Safe Hybrid Relay Rev B (4 pages)
- E-SAFE II Hybrid Power Switch (4 pages)
- EZwarePlus Programming (264 pages)
- EZ-ZONE PM (111 pages)
- EZ-ZONE PM PID (125 pages)
- EZ-ZONE PM Express Limit (34 pages)
- EZ-ZONE PM Express (35 pages)
- EZ-ZONE PM Integrated Controller (181 pages)
- EZ-ZONE RM Limit Module Rev C (127 pages)
- EZ-ZONE RMA Modul (79 pages)
- EZ-ZONE RMC (236 pages)
- EZ-ZONE RME (124 pages)
- EZ-ZONE RMH (161 pages)
- EZ-ZONE RUI/Gateway (62 pages)
- EZ-ZONE RM-Scanner-Modul (140 pages)
- EZ-ZONE ST (97 pages)
- F4 External Event Board - Rev.B (2 pages)
- HG Series Mercury Displacement Relay (6 pages)
- LogicPro (296 pages)
- Mercury Relay or MDR Retrofit (13 pages)
- MICRODIN (24 pages)
- MICRODIN (106 pages)