beautypg.com

Cas200 current inputs, Cas200 current inputs 83, Figure 5.6— cas200 input circuit 83 – Watlow CAS200 User Manual

Page 95

background image

CAS200 User’s Guide

Chapter 5: Troubleshooting and Reconfiguring

Watlow Anafaze

83

Figure 5.6 shows the schematic for one single-ended sensor
input to the CAS200. See CAS200 Current Inputs on page
83
and
CAS200 Voltage Inputs on page 84 for specific
instructions and resistor values for voltage and current
inputs.

Figure 5.6

CAS200 Input Circuit

CAS200 Current Inputs

For each current input on a CAS200 scanner, you must
install one resistor. The value of the resistor must be
correct for the expected input range. Install the resistor in
the listed resistor location.

Table 5.3

Resistor Values for CAS200
Current Inputs

Resistor tolerance:

±

0.1%

Input Range

Resistor Value RD

0 - 10mA

6.0

0 - 20mA

3.0

IN +

RD

Analog

Input

Terminals

RC

Com

To CAS200

Circuitry

(Voltage only)

(Voltage and Current)

Measurement