Chapter 5: Troubleshooting and Reconfiguring

CAS200 User’s Guide

70

Watlow Anafaze

Other Behaviors

The following table indicates potential problems with the
system or scanner and recommends corrective actions.

Table 5.2

Other Symptoms

Symptom

Possible Causes

Recommended Action

Indicated tempera-
ture not as expected

Scanner not communicating

Sensor wiring incorrect

Noise

See Checking Analog Inputs on page 73.

CAS200 display is
not lit

Power connection incorrect

Check wiring and service. See Wiring the
Power Supply on page 19
.

No EPROM or bad EPROM

Replace the EPROM. See Replacing the
EPROM on page 79.

CAS200 damaged or failed

Return the CAS200 for repair. See Return-
ing Your Unit on page 68
.

CAS200 display is
lit, but keys do not
work

Keypad is locked

See Keys Do Not Respond on page 73.

CAS200 damaged or failed

Return the CAS200 for repair. See Return-
ing Your Unit on page 68
.

Alarm limits or other
settings change

Digital job select feature is
enabled and has changed
jobs

Set JOB SELECT DIG INPUTS TO NONE.
This parameter is only accessible using the
scanner’s keypad and display. See Job
Select Inputs on page 45
.

Acknowledged
alarms reoccur or
alarms fail to be indi-
cated

Power is intermittent

Check wiring and service. See Wiring the
Power Supply on page 19
.

Use a separate dc supply for the scanner.

Provide backup power (UPS).

Analog reference voltage is
overloaded

Disconnect any wiring from the +5V Ref
connection on TB1.

Hardware failure

Check the scanner front panel for a hard-
ware alarm. See System Alarms on page
69
.

Scanner does not
behave as expected

Corrupt or incorrect values in
RAM

Perform a

NO

-key reset. See NO-Key

Reset on page 78.