Chapter 6: Linear Scaling Examples

CAS200 User’s Guide

88

Watlow Anafaze

Example 1: 4-20mA Sensor

Situation

A pressure sensor that generates a 4-20 milliamp signal is
connected to the scanner. The specifications of the sensor
state that it generates 4mA at 0.0 pounds per square inch
(psi) and 20mA at 50.0 psi.

Setup

The sensor is connected to a loop input set up with a
resistor scaling network to produce 60 millivolts at 20mA.

The INPUT TYPE for the loop is let to LINEAR. The sensor
measures psi in tenths, so the DISP FORMAT is set to
-999.9 TO +3000.0.

Table 6.1

Input Readings

The scaling values set up in the SETUP LOOP INPUT menu
are shown in Table 9.2.

Table 6.2

Scaling Values

Process
Variable

Displayed

Sensor

Input

Reading, Percent of

Full Scale (%FS)

50.0 psi

20mA

100%FS

0.0 psi

4mA

100% x (4mA/20mA) = 20%FS

Parameter

Prompt

Value

High Process Variable

HIGH PV

50.0 psi

High Sensor Reading

HIGH RDG

100.0%FS

Low Process Variable

LO PV

0.0 psi

Low Sensor Reading

LO RDG

20.0%FS