Example 1: 4-20ma sensor, Situation, Setup – Watlow CAS200 User Manual
Page 100: Example 1: 4-20ma sensor 88, Situation 88, Setup 88
Chapter 6: Linear Scaling Examples
CAS200 User’s Guide
88
Watlow Anafaze
Example 1: 4-20mA Sensor
Situation
A pressure sensor that generates a 4-20 milliamp signal is
connected to the scanner. The specifications of the sensor
state that it generates 4mA at 0.0 pounds per square inch
(psi) and 20mA at 50.0 psi.
Setup
The sensor is connected to a loop input set up with a
resistor scaling network to produce 60 millivolts at 20mA.
The INPUT TYPE for the loop is let to LINEAR. The sensor
measures psi in tenths, so the DISP FORMAT is set to
-999.9 TO +3000.0.
Table 6.1
Input Readings
The scaling values set up in the SETUP LOOP INPUT menu
are shown in Table 9.2.
Table 6.2
Scaling Values
Process
Variable
Displayed
Sensor
Input
Reading, Percent of
Full Scale (%FS)
50.0 psi
20mA
100%FS
0.0 psi
4mA
100% x (4mA/20mA) = 20%FS
Parameter
Prompt
Value
High Process Variable
HIGH PV
50.0 psi
High Sensor Reading
HIGH RDG
100.0%FS
Low Process Variable
LO PV
0.0 psi
Low Sensor Reading
LO RDG
20.0%FS