Outputs, Digital outputs, Outputs 101 – Watlow CAS200 User Manual
Page 113
CAS200 User’s Guide
Chapter 7: Specifications
Watlow Anafaze
101
Outputs
The scanner provides open-collector outputs. These outputs
are typically used to control SSRs or other power switching
devices which in turn may be used to signal another device
of an alarm condition.
An open-collector CPU watchdog output is also provided so
that an external device may monitor the CPU state.
Digital Outputs
Table 7.16
Digital Outputs Control / Alarm
Table 7.17
CPU Watchdog Output
Parameter
Description
Number
35
Operation
Open collector output; ON state sinks to logic common
Function
34 may be used to signal an alarm on one or more channels.
1 global alarm output
Off State Leakage Current
<0.01mA to dc common
Maximum Current
60mA for each output. 5V power supply (from the processor
module) can supply up to 350mA total to all outputs
Maximum Voltage Switched
24Vdc
Parameter
Description
Number
1
Operation
Open collector output; ON state sinks to logic common
Function
Monitors the processor module microprocessor
Maximum Current
10mA (5V power supply in the processor module can supply
up to 35mA total to all outputs)
Maximum Voltage Switched
5Vdc