CAS200 User’s Guide

Chapter 6: Linear Scaling Examples

Watlow Anafaze

89

Example 2: 0-5Vdc Sensor

Situation

A flow sensor connected to the scanner measures the flow
in a pipe. The sensor generates a 0-5V signal. The sensor's
output depends on its installation. Independent calibration
measurements of the flow in the pipe indicate that the
sensor generates 0.5V at three gallons per minute (GPM)
and 4.75V at 65 GPM. The calibration instruments are
accurate to within one gallon per minute.

Setup

The sensor is connected to a loop input set up with a
resistor voltage divider network to produce 60mV at 5V.

The INPUT TYPE for the loop is set to LINEAR. The
calibrating instrument is ±precise to ±1 GPM, so the DISP
FORMAT

is set to -999 TO +3000.

This table shows the input readings and percentage
calculation from the 60mV full scale input.

Table 6.3

Input Readings and Calculations

Table 6.4

Scaling Values

Process
Variable

Displayed

Sensor

Input

Reading, Percent of

Full Scale (%FS)

65 GPM

4.75

(4.75V/ 5.00V) x 100% = 95%

3 GPM

0.5

(0.5V/ 5.00V) x 100% = 10%

Parameter

Prompt

Value

High Process Variable

HIGH PV

65 GPM

High Sensor Reading

HIGH RDG

95.0%FS

Low Process Variable

LO PV

0.0 GPM

Low Sensor Reading

LO RDG

10.0%FS