Chapter 6: Linear Scaling Examples
Watlow Anafaze
89
Example 2: 0-5Vdc Sensor
Situation
A flow sensor connected to the scanner measures the flow
in a pipe. The sensor generates a 0-5V signal. The sensor's
output depends on its installation. Independent calibration
measurements of the flow in the pipe indicate that the
sensor generates 0.5V at three gallons per minute (GPM)
and 4.75V at 65 GPM. The calibration instruments are
accurate to within one gallon per minute.
Setup
The sensor is connected to a loop input set up with a
resistor voltage divider network to produce 60mV at 5V.
The INPUT TYPE for the loop is set to LINEAR. The
calibrating instrument is ±precise to ±1 GPM, so the DISP
FORMAT
is set to -999 TO +3000.
This table shows the input readings and percentage
calculation from the 60mV full scale input.
Table 6.3
Input Readings and Calculations
Table 6.4
Scaling Values
Process
Variable
Displayed
Sensor
Input
Reading, Percent of
Full Scale (%FS)
65 GPM
4.75
(4.75V/ 5.00V) x 100% = 95%
3 GPM
0.5
(0.5V/ 5.00V) x 100% = 10%
Parameter
Prompt
Value
High Process Variable
HIGH PV
65 GPM
High Sensor Reading
HIGH RDG
95.0%FS
Low Process Variable
LO PV
0.0 GPM
Low Sensor Reading
LO RDG
10.0%FS