Display resolution, Display resolution 51 – Watlow CAS200 User Manual
Page 63
CAS200 User’s Guide
Chapter 4: Setup
Watlow Anafaze
51
NOTE!
If you set the input type to Skip, you won't see any
of the other submenus in the Setup Channel Input
menu. Channel #17 toggles between pulse and
skip. If you set the input type to any thermocou-
ple, you will see the Offset menu. If you set the in-
put type to Linear, or you are editing the Pulse
channel (#17), you will see the Input Scaling sub-
menus.
Selectable values: The table shows the input types and
ranges.
Display Resolution
When type T thermocouples are selected the display may be
in tenths of a degree or whole number.
Selectable values: -999 to 999 or -999.0 to 999.0
Input Type
Fahrenheit
Range
Celsius Range
J
-350 to 1400
-212 to 760
K
-450 to 2500
-268 to 1371
T
-450 to 750
-18 to 1766
S
0 to 3200
-18 to 1760
R
0 to 3210
-18 to 1765
B
+150 to 3200
+66 to 1760
PL-II
+50 to 2012
+10 to 1100
N
-450 to 2370
-268 to 1299
Pulse
0-2KHz (Channel #17 only)
Skip
Channel is not scanned or
displayed
Linear
See the Linear Scaling section
(this chapter) and appendix.
CHANNEL PROCESS UNITS
CHANNEL NAME ALARM STATUS
01 DISP RES?
-999 to 999