HW Ambient Failure

The hardware failure ambient alarm indicates that the
ambient sensor in the CAS200 is reporting that the
temperature around the scanner is outside of the
acceptable range of 0-50˚ C. This error can also occur when
there is a hardware failure.

If the scanner displays HW AMBIENT FAILURE:

1.

Check the ambient air temperature near the scanner.
Adjust ventilation, cooling or heating to ensure that
the temperature around the scanner is 0-50˚ C. If the
unit is functioning correctly, the error will clear
automatically when the ambient temperature is
within range.

2.

If the ambient temperature is within range and the er-
ror persists:

a)

Turn n the power to the scanner off.

b) Remove the boards from the CAS200 housing.

c)

Reseat the boards and turn power on.

3.

If the error persists, make a record of the settings,
then perform a

NO

-key reset. See NO-Key Reset on

page 78.

4.

If the error is not cleared, contact your supplier for fur-
ther troubleshooting guidelines. See Returning Your
Unit on page 68.

NOTE!

If the scanner has failed, it is likely that it was
damaged by excessive voltage or noise. Before
replacing the scanner, troubleshoot for noise and
ground channels.

HW Gain or Offset Failure

If the scanner displays HW FAILURE GAIN or HW FAILURE
OFFSET

:

1.

Turn the power to the scanner off, the on again.

2.

If the error persists, make a record of the settings (us-
ing software), then perform a

NO

-key reset. See NO-

Key Reset on page 78.

3.

If the error is not cleared, contact your supplier for fur-
ther troubleshooting guidelines. See Returning Your
Unit on page 68.