EVENT CODES AND TRANSITION MESSAGES

Table 7-2. Event Codes, Description and Action (Cont’d)

Block

Type

Codes

Full Message Text

Description/Action

MSC

4

MODULE MISMATCH

The slot(s) configured for a MODBUS
communications module is either empty or the
installed module does not match the slot
configuration.

MSC

5

MESSAGE CHECK ERROR

A received message could not be processed
because it failed the Cyclical Redundancy
Check (CRC) check.

MSC

6

PARITY ERROR

A parity error was detected for a received byte.
The message is discarded.

MSC

7

BREAK ERROR

A break sequence was detected (a character
with zero value and framing error was received)
by the 68032 for a received byte. The
message is discarded.

MSC

8

FRAMING ERROR

No stop bit was detected by the 68032 for a
received byte.

MSC

9

NOISE ERROR

The 68302 checked a bit three times and the
three samples were not identical.

MSC

10

OVERRUN ERROR

The central processor could not store a
received byte before the next byte was
received.

MSC

11

INVALID MESSAGE

The message length was too large, the
message size was incorrect, or there was an
illegal use of a global message. The message
is discarded.

MSC

12

EXCESS MESSAGES FOR PORT

The receive buffer for this port had no room for
the message being received. A message is
lost.

MSC

13

EXCESS MESSAGES FOR TASK

The maximum number of requests queued for a
group has been reached. A message is lost.

MSC

14

DEFAULT COMM SWITCH SET

The default communication switch is set (yes)
on the RS-232 or RS-485 module. Therefore,
this block is functioning as a SLAVE using 9600
baud, no parity and one stop bit for it’s
communication parameters.