Micromod MOD: 30ML and Modcell Maintenance for 2001N, 2002N, and 1800R User Manual
Page 99
MOD30ML and Modcell Maintenance Manual
EVENT CODES AND TRANSITION MESSAGES
Table 7-2. Event Codes, Description and Action (Cont’d)
Block
Type
Codes
Full Message Text
Description/Action
MSC
4
MODULE MISMATCH
The slot(s) configured for a MODBUS
communications module is either empty or the
installed module does not match the slot
configuration.
MSC
5
MESSAGE CHECK ERROR
A received message could not be processed
because it failed the Cyclical Redundancy
Check (CRC) check.
MSC
6
PARITY ERROR
A parity error was detected for a received byte.
The message is discarded.
MSC
7
BREAK ERROR
A break sequence was detected (a character
with zero value and framing error was received)
by the 68032 for a received byte. The
message is discarded.
MSC
8
FRAMING ERROR
No stop bit was detected by the 68032 for a
received byte.
MSC
9
NOISE ERROR
The 68302 checked a bit three times and the
three samples were not identical.
MSC
10
OVERRUN ERROR
The central processor could not store a
received byte before the next byte was
received.
MSC
11
INVALID MESSAGE
The message length was too large, the
message size was incorrect, or there was an
illegal use of a global message. The message
is discarded.
MSC
12
EXCESS MESSAGES FOR PORT
The receive buffer for this port had no room for
the message being received. A message is
lost.
MSC
13
EXCESS MESSAGES FOR TASK
The maximum number of requests queued for a
group has been reached. A message is lost.
MSC
14
DEFAULT COMM SWITCH SET
The default communication switch is set (yes)
on the RS-232 or RS-485 module. Therefore,
this block is functioning as a SLAVE using 9600
baud, no parity and one stop bit for it’s
communication parameters.
7 -12