beautypg.com

Technical notice, Solution, Built-in input 1 configured as b type t/c – Micromod MOD: 30ML and Modcell Maintenance for 2001N, 2002N, and 1800R User Manual

Page 134

background image

Technical Notice

Dynamic Compensation: Since this Type of thermocouple has a curve that produces almost no signal a

room temperature, dynamic compensation really is not necessary. The millivolt value in a Type B curve

that corresponds to 23 degrees C is -0.003 mV. At normal operating temperatures (above 800 degrees

C), this relates to about 1/3 of a degree offset. Adding a fixed compensation value is all that is necessary

for this type of thermocouple.

Using dynamic compensation may not help since the Type B tables indicate that the mV signal will

fluctuate between 0.000 and -0.003 for any temperature under 45 degrees C.

Solution:

The solution to this problem is to perform the linearization manually with other blocks. We will use an EX

(expression) block and a LN (linearization) block to this. This is explained below with configuration in

ViZapp. If you use Application Builder, you can still follow the steps below. If you configured the controller

from the front face, consider configuring it from the ViZapp or Application Builder software as the fix

involves EX and LN blocks. The solution is different for Built-in inputs and Module inputs. Both types are

discusseed below. The following 3 schemes are discussed in this Technote:

1. Built-In input 1 in MOD 30ML configured as B type thermocouple

2. Built-In input 2 in MOD 30ML configured as B type thermocouple

3. Thermocouple module 2013A configured as B type thermocouple in MOD 30ML or Modcell

Note: The Default Gallary in VIZapp includes these schemes as compounds. You can also simply

load the compound and use it.

Built-In Input 1 configured as B type T/C:

1. This scheme requires an AIN block, EX blocks and a LN block in your control strategy as shown in

the next figure

2. Configure the AIN block for B type thermocouple and the desired Temperature scale.

3. Configure the first EX block’s (mV2uVBI1) General tab as shown in the figure below: (Tag names and

descriptions are optional).

Topic: MOD 30ML/Modcell

Technote: TNML0501-1

MicroMod Automation, Inc.

Rev. May-2001

B Type TC Problem.Doc

Page 2 of 6