MOD30ML and Modcell Maintenance Manual

EVENT CODES AND TRANSITION MESSAGES

Table 7-2. Event Codes, Description and Action (Cont’d)

Block

Type

Codes

Full Message Text

Description/Action

EX

0

BLOCK STATE SET TO RUN

Information only.

EX

1

BLOCK STATE SET TO HOLD

Information only.

EX

2

BLOCK STATE SET TO OFF

Information only.

EX

3

BLOCK STATE SET TO DEBUG

Information only.

EX

4

CALCULATION ERROR

One of the following conditions was detected:
• There is a calculation error (calculation

overflow, divide by zero, square root of
negative number etc.). The block completes
the calculation using some reasonable value
(+ or - maximum value for overflows, zero for
square root of negative number, etc.), and
sets the output quality bad if Attribute No. 10,
Set quality bad on calculation error?
(SETQBAD) is YES. The diagnostic error
clears and the quality is set back to good
when a subsequent execution of the block
performs a successful calculation.

• Improper syntax in the expression.
• A stack overflow due to too many nested

operations.

IC

0

BLOCK STATE SET TO RUN

Information only.

IC

1

BLOCK STATE SET TO HOLD

Information only.

IC

2

BLOCK STATE SET TO OFF

Information only.

IC

3

BLOCK STATE SET TO DEBUG

Information only.

IC

4

RECEIVING UNEXPECTED MESSAGE

There is a configuration error (source or data
type incorrect) within either this block or within
an Output Communication block in another
instrument.

IC

5

NOT RECEIVING DATA

A break in the communications has halted the
continual flow of data from the source. No new
data has been received for 2 seconds.

IC

6

BLOCK MODE SET TO MANUAL

Information only.

IC

7

BLOCK MODE SET TO AUTO

Information only.

7 -5