MOD30ML and Modcell Maintenance Manual

DIAGNOSING SHUTDOWN FAULTS

3. With power off, install the memory module in an operable spare instrument (either

MODCELL or MOD 30ML).

4. Apply power to the instrument.

5. Start the Application Builder Software. If communication to the instrument is via an RS-

232 or RS-485 port, the default parameters (9600 baud, no parity, 8 data bits, 1 stop bit)
must be used. See Section 3 for the software startup procedure.

6. Access the status display in the application builder.

7. On the Instrument Status display command line, type the command R SD M and click on

ENTER. A display providing shutdown data appears. A form illustrating this display with
blank data fields is provided at the end of this section.


NOTE: If a facility for printing the display screen is available, it can be used to generate a
copy of the shutdown data.

8. Make a copy of the form and fill in the blank fields on the copy using the data from the

display.

9. Copy the Catalog number and Version number from the identity module in the failed

instrument onto the shutdown data form.

10. Keep a copy of the completed shutdown information for future reference.