MOD30ML and Modcell Maintenance Manual

COMMUNICATIONS

Message

Probable Cause

Action

Error writing .ID1 or .ID2 file




Instrument data base file (.ID1) or
LCP data base file (.ID2) cannot
accept data because:
1. Disk is full.
2. Wrong drive selected.
3. Diskette not installed.




1. Provide more disk space
2. Select correct drive
3. Install

diskette.

Error writing .SD1 file

Shutdown data file (.SD1) cannot
accept data because disk is full.

Provide more disk space.

GetAddress: Unspecified Error

This error occurs while entering
one of the following modes:
Status, Upload or Download in
ViZapp.

Device name specified in the
Communication Setup dialog box
(See Section 3.3.4 or 3.3.5) does
not exist in the OPC Server
database.

No device is selected in the
Communication setup dialog box
in ViZapp

1. Select a device from the OPC

Server database by clicking on
the Browse button in the
Communication Setup dialog
box.

2. If the device name does not

exist in the OPC Server
database, add it.

ICN timeout - no response from
instrument

1. Instrument power is off.
2. Configured ICN number or

instrument number does not
exist.

3. Termination facility on front of

MODCELL Eurocard
instrument not properly
engaged.

4. MOD 30ML instrument not

fully seated in its housing.

1. Turn on power.
2. Check communications setup

(see Section 3.2.2).

3. Tighten housing screw, Figure

1.

4. Push instrument into housing

and tighter front panel
retaining screws.

Import aborted

Information only

This message follows the report of
error(s), which must be corrected
before the import can be
successfully completed.

Import completed without error

Information only

None

In service manual

RUN/SERV switch is in SERV.

Set switch at RUN

In valid data type

Specified data type is invalid.
e.g., RS IF1,TIME or RS EX1,I3 F
(RS can only be used with hex or
ASCII data)

Correct entry and try again. See
Section 3.4.3.

Inst in hold state

A write command to change the
instrument STATE to RUN cannot
be accepted because the
RUN/SERV switch is set at
SERV.

If process condition is ready for
normal operation, change switch
setting to RUN.

Instrument is not a LCP

Upload or download of LCP
database failed because
instrument at the configured
address is not an LCP.

Verify that instrument at address
configured on LCP Utility menu is
an LCP