beautypg.com

Micromod MOD: 30ML and Modcell Maintenance for 2001N, 2002N, and 1800R User Manual

Page 93

background image

MOD30ML and Modcell Maintenance Manual
EVENT CODES AND TRANSITION MESSAGES

Table 7-2. Event Codes, Description and Action (Cont’d)

Block

Type

Codes

Full Message Text

Description/Action

ICN

4

MODULE MISMATCH

The slots configured for an ICN
communications module are either empty or the
installed module does not match the slot
configuration.

ICN

5

ACCESS TIMEOUT

Access to transmit has not been granted for at
least one second. Token ring is broken, ICN
restarted.

ICN

6

RESTART FAILURE

Communications cannot be established.

ICN

7

INVALID MESSAGE

The message code of a received message was
invalid or is not supported by the software.

ICN

8

MESSAGE DATA INVALID

A received message could not be processed
because it failed the CRC check.

ICN

9

FRAMING ERROR

No stop bit was detected by the 68032 for a
received byte.

ICN

10

NOISE ERROR

The 68302 checked a bit three times and the
three samples were not identical.

ICN

11

OVERRUN ERROR

The central processor could not store a
received byte before the next byte was
received.

ICN

12

INVALID MESSAGE SIZE

The size of the message or its data field is
invalid.

ICN

13

EXCESS MESSAGES RECEIVED

The receive buffer for this port had no room for
the message being received. A message is
"lost".

ICN

14

EXCESS MESSAGES TO TRANSMIT

The buffer used for the messages to be
transmitted had no room for another. A
message is "lost".

ICN

15

UNEXPECTED COMM MESSAGE
RECEIVED

An input communications message was
received, but the occurrence for which it was
destined is not in the current configuration.

ICN

16

COMMUNICATION OVERLOAD

The time for each instrument on the ICN to
transmit all messages exceeded the
recommended time of 250 msec.

ICN

17

EXCESS MESSAGES FOR TASK

The maximum number of requests queued for a
group has been reached. A message is "lost".

7 -6