MOD30ML and Modcell Maintenance

VIEWING DIAGNOSTIC DATA

Event Code and Message Text - Each diagnostic in a block has a unique code

number (8 in the example), and a brief text message (WRIM MODULE ERROR) is
appended to the code to indicate the nature of the problem.

Use the block type and event code to locate the diagnostic description and corrective action
listed in Section 7. The description/action listed for WRIM, code 8 states that the module has
reported an extended error code, and references Section 5, which provides detailed
information about the error.

Figure 3. 22. Instrument Status – Application Builder


Another example of the message returned in response to an R DIAGS command is:

IF1 ACK_ONLY UAK G CLR G

14 INSTRUMENT POWERED UP

IF1 ACK_ONLY UAK G CLR G

14 INSTRUMENT POWERED DOWN

This message, as it appears on the status display, is shown in the next figures for viZapp.
The information contained is as follows:

Block Type and Occurrence Number - This identifies the block reporting the

diagnostic (IF1 in the example).

Classification of the diagnostic:

o NEW/CLR - Diagnostics having a sustained active state, which is cleared

when normal conditions are restored.