beautypg.com

Micromod MOD: 30ML and Modcell Maintenance for 2001N, 2002N, and 1800R User Manual

Page 91

background image

MOD30ML and Modcell Maintenance Manual
EVENT CODES AND TRANSITION MESSAGES

Table 7-2. Event Codes, Description and Action (Cont’d)

Block

Type

Codes

Full Message Text

Description/Action

DDOM

4

BLOCK MODE_1 SET TO AUTO

Information only.

DDOM

5

BLOCK MODE_1 SET TO MANUAL

Information only.

DDOM

6

BLOCK MODE_2 SET TO AUTO

Information only.

DDOM

7

BLOCK MODE_2 SET TO MANUAL

Information only.

DDOM

8

I/O MISMATCH

A slot configured for a digital module contains
an intelligent module (analog input, analog
output, ICN, MSC or RIO).
NOTE: This diagnostic cannot distinguish
between an empty slot and a digital I/O module
or between different types of digital modules.

DDOM

9

DDO_1_MODULE_ERROR

The select circuit, which is used to
communicate with the module blocks, has a
diagnostic error. In this case, all modules
report this diagnostic.

DDOM

10

DDO_2_MODULE_ERROR

Same as Code 9.

DI

0

BLOCK STATE SET TO RUN

Information only.

DI

1

BLOCK STATE SET TO HOLD

Information only.

DI

2

BLOCK STATE SET TO OFF

Information only.

DI

3

BLOCK STATE SET TO DEBUG

Information only.

DIF

4

FACEPLATE COMMUNICATIONS ERROR An error occurred when trying to communicate

with the faceplate. Instances are counted in
CMERRCTR or BFULLCTR.

DIF

5

NO KEYBOARD RESPONSE

The faceplate failed to respond when keyboard
data was requested. Instances are counted in
KBERRCTR.

DIM

4

BLOCK MODE SET TO AUTO

Information only.

DIM

5

BLOCK MODE SET TO MANUAL

Information only.

DIM

6

I/O MISMATCH

A slot configured for a digital module contains
an intelligent module (analog input, analog
output, ICN, MSC or RIO).
NOTE: This diagnostic cannot distinguish
between an empty slot and a digital I/O module
or between different types of digital modules.

DISP

4

INVALID DISPLAY OPERATION
ATTEMPTED (Ack Only Diag).

This error is reported if for example, an attempt
is made (via key event statement or remote
source) to perform some illegal operation.

DOM

4

BLOCK MODE SET TO AUTO

Information only.

DOM

5

BLOCK MODE SET TO MANUAL

Information only.

DOM

6

I/O MISMATCH

A slot configured for a digital module contains
an intelligent module (analog input, analog
output, ICN, MSC or RIO).
NOTE: This diagnostic cannot distinguish
between an empty slot and a digital I/O module
or between different types of digital modules.

DOM

7

DO_MODULE_ERROR

The select circuit, which is used to
communicate with the module blocks, has a
diagnostic error. In this case, all modules
report this diagnostic.

7 -4