Table 5 .3. Analog Output Module Extended Error (EXTERR) Codes
Bit/Value
Status Display Message
Problem
Action
15 Unused
-----------------
-----------------
14/1
Read-back is zero
1. Incorrect connection to
module terminals
2. Module Error and Read
back Error
3. Fault in module or
Continuous error or
physical output errors
1. Verify
connections
(see IB-23C600)
2. Refer to the technical
note TNML1001-2.
See Appendix.
3. Replace
module
14/0
No message
Read-back is OK
None
13 Unused
-----------------
-----------------
12/1
Global error is indicated
An error has been detected
See error messages (bits
0-6)
12/0
No message
No error
None
11/1
Read-back is invalid
Fault in module
Replace module
11/0
No message
Read-back is OK
None
10/1
Read-back is out of range
Fault in module
Replace module
10/0
No message
Read-back is OK
None
9/1
In calibration mode
Status report
None
9/0
In standard mode
Status report
None
8 Unused
-----------------
-----------------
7/1*
Power-up or watchdog
timeout
1. Power-up
not
acknowledged
2. Acknowledge does not
clear power-up.
1. Acknowledge
power-
up
2. Replace
module
6/1*
Configuration checksum error
Fault in module
Replace module
5/1*
Host communications invalid
command error
Fault in module
Replace module
4/1*
EEPROM Calibration data
error
Fault in module
Replace module
3/1* EEPROM
communications
error
Fault in module
Replace module
2/1*
Host communications register
range error
Instrument trying to write to
unauthorized register
If error is repeated replace
module
1/1* Host
communications
checksum errors
Fault in module
Replace module
0/1*
Failsafe timeout
Fault in module
Replace module
*0 = No Error