2.0 Loop Power Application

The VMA will provide 24VDC Loop Power for transmitter loop circuits. The recommended wiring is depicted in
the diagram below:











Diagram 2.1 – Loop Power Connection Diagram for simple low load loop


Connect the test circuit according to the Diagram 2.1.
Include 250-ohm resistor for low load loops.
The loop power is turned on from the MFT

Measure Mode by pressing the following keys:

Press

the

More Soft Key two times

Press

the

Pon Soft Key to turn VMA power supply on


















The SX sensor location (depending which bay the VMA is located in) should read approximately 24.00 VDC. The
MFT’s IV value will read the loop current.

To establish HART communications with the test device, press the MFT’s

HART key.



VOLTS

COM

mA

MFT
HART

Transmitter

VMA

Module

-

+

-

+

MFT

mA/V Meter

Measure

S1: 24.00 V

S2: 0.000 PSIG

S3: 72.05 deg F

IV: 4.000 mA



Pon Poff Vrng More