Meriam MFT 4010 Modular Calibrator_HART Communicator User Manual

Page 35

background image

30












Upper Sensor Trim Screen

Apply a high pressure value to the HART device (100 inW20C shown above) and allow it to stabilize. The
actual value chosen for this pressure point is at the operator’s discretion. When the S1 sensor (or whichever
sensor is selected) reads a steady high pressure value, press the Trim soft key. The sensor will
automatically be trimmed to match the MFT measured value, and the screen will display the prompt:
Remove Pressure. This notice reminds the user to release the pressure applied. Press OK to continue.
The screen will now prompt: Put Loop back online. This notice reminds the user to reconnect the device
under test to the receiving device. Press the OK soft key to continue.

Press the Back soft key to return to the Hart Smart Trim Screen main menu screen. Pressing Back again
will return the MFT to the Calibration key main menu screen.


View Results: Allows users to view saved calibration results. Selecting this menu option provides the user with
a summary of saved calibration files, soft key functions used for viewing the information, and a delete file
function.

Use the Up or Down soft key to move the selection arrow to View Results, then press the Select soft key.
The following screen will appear.










Move the selection arrow to the tag number desired and press the Select soft key. Point one of the saved
calibration is displayed as shown below.












Cal
Select Cal to view:

PT-102

PT-307
DPT-101
DPT-106
TT-621

Up Down Select Back

Trim Upper
Cal: Pump 8

PV: 99.692 InH20


MFT Upper Sensor
S1: 100.00 inW20C


Up Down Select Back